Score: 22

#  Comments Points
3. pH too low. Must be between 7.2-7.8 at all times. Recommend between 7.4-7.6. 6.0
5. Must have a National/WCES CPO inspect pool at least once per day 7days a week! Must post all CPO certificates in the pump room! Need at least 2 National/WCES CPO on staff to provide the 7days a week coverage! This is a WCES 6pt closure item! Must have an inspection by a National/WCES CPO whose licenses are posted in the room prior to calling for the reinspection. They must inspection pool 1x/day 7days a week. 4.0
17. Need to repair damaged tiles by ladder. Must be repaired by permitting! 4.0
22. Phone not working. Required at all times 6.0
24. 18,850gal; 52gpm min turnover flowrate. 0.0
25. Store all chemicals in the chemical storage room and 12inches off the floor! 2.0
General Comments
Pool closed by WCES but allowed to be posted closed by management. Pool must remain closed until all 6pt closure items are corrected and a reinspection by WCES is completed and pool reopened by WCES. Call 919.604.4302 to schedule the reinspection once all 6pt closure items are corrected.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 02/16/2024
Score: 10

#  Comments Points
2. Recommend between 3-5 0.0
3. Recommend between 7.4-7.6 0.0
5. Must have a National/WCES CPO inspect pool at least once per day 7days a week! Must post all CPO certificates in the pump room! Need at least 2 National/WCES CPO on staff to provide the 7days a week coverage! This will be a WCES 6pt closure item at next occurrence! 4.0
24. 18,850gal; 52gpm min turnover flowrate. Must repair or replace the flow meter! 4.0
25. Store all chemicals in the chemical storage room and 12inches off the floor! 2.0
General Comments
Issued year round indoor pool permit with conditions!

Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 09/19/2023
Score: 4

#  Comments Points
5. Must date records. Must have a National/WCES CPO inspect pool at least once per day 7days a week! Need at least 2 National/WCES CPO on staff to provide the 7days a week coverage. Must post all CPO certificates in the pump room! Do not let CPO certificates expire. This can be a WCES 6pt closure item! 4.0
24. ~18,850gal; 52gpm min turnover flowrate 0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 02/17/2023
Score: 8

#  Comments Points
8. One pool skimmer is missing a weir. Please replace. 4.0
9. Replace cracked pool depth marker tile on pool deck adjacent to entry steps. 4.0
24. Pool pump, flow rate, and drain covers were checked during inspection and matched with VGB permit data on file. 0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.

Annual pool permit issued on February 17, 2023.

Pool operation permit expires on February 17, 2024.

Visible bonding wiring was intact and attached to pool pump at the time of inspection.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 12/15/2022
Score: 10

#  Comments Points
3. Recommend between 7.4-7.6 0.0
5. Must have a National/WCES CPO on staff to inspect pool at least once per day 7days a week! Must have readings 2x/day 6hrs apart 7days a week! Need at least 2 National/WCES CPO on staff to provide the 7days a week coverage! This will be a WCES 6pt closure item at next occurrence! 4.0
22. Phone tied to fax line upon arrival! Disconnected during the inspection, points taken but not closing! Do not let fax get connected to the pool line! 6.0
24. ~18,850gal; 52gpm min turnover flowrate. Fix stuck/ broken flowmeter! Flowmeter must be functional at permitting 0.0
29. Provide soap at shower! 0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 02/17/2022
Score: 10

#  Comments Points
5. Must have a National/WCES CPO on staff to inspect pool at least once per day 7days a week! Need at least 2 National/WCES CPO on staff to provide the 7days a week coverage! Must show when pool is closed and reopened due to chemical being off. This can be a WCES 6pt closure item! 4.0
16. Watch emergency exit doors, must be selfclosing/latching at all times! 0.0
17. Watch drainage of water on pool deck. Needs to flow better to drains. 0.0
21. HVAC system is not working properly, high humidity levels causing excess water on ceiling, windows and pool deck. System is being adjusted. Need to correct asap. 4.0
24. 91gpm, 18,850gal; 52gpm min turnover flowrate. 0.0
25. Fix leaks in pump room. Vent fan in chemical room was not functioning properly but repaired during the inspection. Points taken but not closing. 2.0
General Comments
Issued year round indoor pool permit.

Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 11/17/2021
Score: 12

#  Comments Points
5. Must have readings 2x/day 6hrs apart 7days a week. Do not let CPO certificates expire! 4.0
6. Must replace VGB drains and have recertification submitted and approved prior to permitting in February of 2022. Submit the recertification to wcpools@wakegov.com. 0.0
22. Phone not working properly, tied to fax line. Corrected during the inspection, points taken but not closing! Do not share pool phone line with any other phone! 6.0
29. Repair convenience bathroom sink. 2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.

Indoor pool.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 02/17/2021
Score: 0

#  Comments Points
7. Watch pool walls and floor. Staining starting to occur in random areas. Recommend starting process to redo pool plaster/shell. 0.0
General Comments
Issued year round indoor pool permit.

Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.

This pool must remain closed until the local and state closure orders currently in effect as a result of the COVID-19 pandemic are terminated.

Pool staff and patrons are strongly encouraged to comply with the most current CDC guidance concerning social distancing related to the COVID-19 pandemic.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 01/07/2021
Score: 14

#  Comments Points
17. Tiles at ladders raised and slightly loose but are not 1/2 inch trip hazard. Must repair. 4.0
22. Phone keys sticking, repaired during the inspection. Points taken but not closing. Recommend replacing phone and having spare phone available at all times. 6.0
24. Fix leaks. Ground wire is not connected between the pool and the heater. This is a state 6pt closure item! Must have an electrician obtain an electrical permit from the appropriate municipality and have the new connected ground wire inspected. Must provide a copy of the completed electrical permit before a reinspection can be scheduled. Email a copy to ed.duke@wakegov.com 4.0
General Comments
Pool closed and posted closed by management. Must correct 6pt closure items and provide copy of the completed electrical permit before calling 919-604-4302 to schedule the reinspection. Pool permit expires on 1-8-21, so new permit required to be issued at the reopening inspection after repairs made.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 10/06/2020
Score: 8

#  Comments Points
5. Must have a National/WCES CPO inspect pool at least once per day of the 2 required inspection. Need 2 National/WCES CPO on staff. This can be a WCES 6pt closure item! 4.0
16. Emergency doors not selfclosing/latching but repaired during the inspection. Points taken but not closing. 4.0
22. Recommend having a second phone to allow switching and treating phone for moisture buildup. Must check phone every day to ensure all keys functional. 0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.

This pool must remain closed until the local and state closure orders currently in effect as a result of the COVID-19 pandemic are terminated.

Pool staff and patrons are strongly encouraged to comply with the most current CDC guidance concerning social distancing related to the COVID-19 pandemic.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 01/08/2020
Score: 0

#  Comments Points
General Comments
Issued year round pool permit.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 12/11/2019
Score: 0

#  Comments Points
5. Keep CPO license posted. 0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 01/11/2019
Score: 4

#  Comments Points
2. Lower to 3-5 0.0
5. Must take 2x/day 7days/week Must renew national and Wake County cpo soon. Do not let expire! 4.0
22. Add pool to 911 description 0.0
General Comments
Permit issued to indoor year round pool.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 12/12/2018
Score: 16

#  Comments Points
3. Lower between 7.4-7.6 0.0
15. Reattach rope to ring buoy! Closure item! 6.0
17. Watch deck at strip grate for trip hazard. Check also for drainage for showers. 4.0
22. Phone number is displaying incorrect information at 911! Also having to dial 9 to get an outside line. Phone must be able to direct dial out all numbers and not go through a switch board. Pool to remain closed till phone number corrected at 911 and a reinspection performed by Wake County. 6.0
General Comments
Pool closed due to phone and ring buoy/rope. Call 919-604-4302 to schedule the reinspection when phone and buoy/rope are corrected. Pool posted closed by facility.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 04/27/2018
Score: 4

#  Comments Points
5. Must have WC/national authorized CPO inspecting pool at least 1/day. Must have 2 inspections 6 hrs apart 7 days a week. 0.0
17. Watch deck at strip grate for trip hazard. Check also for drainage for showers. 4.0
22. Add pool to 911 description. 0.0
23. Salt water pool 0.0
24. 45gpm; 36psi 0.0
General Comments
Indoor Year Round pool.

Permit issued.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 04/25/2018
Score: 18

#  Comments Points
5. Must have WC/national authorized CPO inspecting pool at least 1/day. Must have ve 2 inspections 6 hrs apart 7 days a week. 4.0
17. Watch deck at strip grate for trip hazard. Check also for drainage for showers. 4.0
22. Phone is direct dail to 911 and does not have correct number assigned to it. Change phone to non direct dail and post sign with correct number that is assigned to it at 911. 6.0
24. 40psi; 40gpm 4.0
General Comments
Pool closed till phone is corrected. Call 919-604-4302 to schedule reinspection. Pool posted closed by owner.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Hyatt House Brier Creek Pool
Location: 10030 Sellona ST RALEIGH, NC 27617
Facility Type: Year-Round Swimming Pools
Inspection Date: 12/21/2017
Score: 0

#  Comments Points
General Comments
Initial opening inspection.
$275 Pool permit fee provided. Receipt given to Kenyetta Parker
Red Denotes Critical Violation