PARTNERSHIP ELEMENTARY SCHOOL


601 DEVEREUX ST
RALEIGH, NC 27605

Facility Type: Schools
 

Related Reports

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 01/18/2024
Score: 92

#  Comments Points
4. Repair chipped and broken floor tiles around the floor drain in the toilet stalls of boy`s bathroom #209. Repair chipped wall covering by the urinals in boy`s bathroom #107. 15.0
6. Repair chipping and peeling paint and plaster on the walls and ceilings of both stairways #1 and #2. The source of moisture intrusion causing the ongoing deterioration of the wall and ceiling surfaces in these stairways should be located and repaired. Chipping and broken cement and plaster is present beneath the steps and the landing platforms on the basement levels of both stairways #1 and #2. Rebar has become exposed and is rusted in these deteriorated areas beneath the steps and landings. These deteriorated supports and the deteriorated materials beneath these stair steps pose concerns for the continued structural stability and safety of the lower stairs. Priority repairs to stabilize and reinforce these stairway steps and landing supports is needed. Repair chipped and deteriorated stair step tops and risers on the basement level of stairway #1. These damaged steps pose the risk of trip and fall hazards and require repairs for safety and stability. The repairs listed for stairways #1 and #2 are repeat items that have been noted of prior sanitation inspection reports. Repair and repaint chipping wall paint and ceiling pipework paint in the basement stockroom at the entrance by stairway #2. 30.0
8. Replace missing ceiling light shield covers on fixtures in the original front stairway at the basement entrance, in the multipurpose room, and over the top floor landing in stairway #5. 20.0
11. Repair and replace broken wooden fence railings around the dumpster pad. 15.0
General Comments
Repair nonfunctional elevator in the school building area adjacent to the lobby and office. School facility sanitation report completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 01/17/2023
Score: 86.5

#  Comments Points
4. Repair toilet in the second stall of girl`s bathroom #115. This toilet has poor water flow for flushing and requires a new flush valve. Repair toilet that is leaking on its pipework in the second stall of girl`s bathroom #206. 20.0
6. Stairway #2 has peeling wall paint, chipped and deteriorated plaster walls, a chipping and peeling ceiling, and chipped plaster on the base support platform beneath the stairs. Stairwell # 2 walls, ceiling, and stair step platform are in need of urgent repair. The chipping plaster on the stairway wall, ceiling, and stair step platform is a safety concern. Chipping on the lowest level of the step platform includes both plaster and cement. Rebar is now exposed on this deteriorated step platform location. Continued deterioration runs the risk of possible structural safety and integrity concerns for the stairwell #2 walls, ceiling, and step platform. There is also a concern of falling plaster in stairwell #2. This a repeat and ongoing inspection item that has been noted in the sanitation inspection reports for 2019, 2020, 2021, and 2022. Chipping and peeling wall paint and plaster is also present in stairwell # 1 The ceiling paint covering in stairway # 1 is also chipping and peeling. There is also chipping paint and plaster beneath the step platform on the lowest level of stairway #1. The walls, ceiling, and base of the step platform in stairway #1 require painting and repair to prevent further deterioration. Stair steps on the lowest level of stairway #1 are chipping and deteriorating and are in need of immediate repair due to potential safety issues. These safety issues include potential trip and fall hazards. The repair items for stairway # 1 were also noted in the facility sanitation inspection for 2022. Repair chipping ceiling covering in the basement work room adjacent to stairway #1. Repair sources of ceiling leaks in the media center that are coming from the boy`s bathroom on the floor above it. Repair source of active ceiling leak in the school lobby. Repair ceiling leaks in the school cafeteria/gym behind the meal service line. Repair ceiling leaks present in classroom #110 by the wall adjacent to the lobby and by the opposite wall with windows. Repair ceiling leak in classroom #104 by the room air conditioning unit. Repair ceiling leak in the ground floor hallway at stairway #5 and the rear entry/exit doors. Replace water stained and damaged ceiling tiles in the listed school locations after the sources of these leaks have been fixed. 30.0
8. Repair and replace broken and loose hanging light fixtures shield coverings in the central stairway # 4 at the ceiling skylight. Priority repairs for safety are necessary due to the possibility of these light fixture coverings falling. Repeat item noted in prior building sanitation inspection. Replace broken ceiling light shield covering in boy`s bathroom #107. Repair nonfunctional ceiling can light fixture in the hallway at the entrance to classroom #202. 40.0
11. Replace or repair damaged ceiling/roof on gazebo on the school playground. Cleaning chemicals including Clorox surface wipes and chemical spray cleaners were left out in areas accessible to students in classrooms throughout the school building. Cleaning chemicals must be stored in areas only accessible by staff. Cleaning chemicals should be stored in areas such as locked or closed cabinets, desks, stock rooms, or closets. Repeat inspection item noted on the prior year`s sanitation inspection report. 45.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 01/13/2022
Score: 90.5

#  Comments Points
5. Repair broken sink drain cap release in the kitchen sink. This sink will not properly drain. 15.0
6. Stairway # 2 has peeling wall paint, chipped and deteriorated plaster walls, and chipped plaster on the base support platform beneath the stairs. Stairwell #2 walls and stair step platform are in need of urgent repair. The chipping plaster on the stairway walls and on the stair step platform is a safety concern. Chipping on the lowest step platform includes both plaster and cement. Rebar is now exposed on this step platform location. Continued deterioration could possibly create structural safety and integrity concerns for both the stair walls and step platform. There is also a concern of falling plaster in this stairwell. This is a repeat inspection violation from the 2019, 2020, and 2021 facility sanitation inspections and has not been addressed. Chipping wall paint is also present in stairway #1. The ceiling covering is also chipping in stairway #1. There is also chipping paint beneath the lowest step platform in stairway #1. The walls, ceiling, and base of step platform in stairway #1 require painting and repair to prevent further deterioration. Stair steps on the lower level of stairway #1 are chipping and deteriorating and are in need of immediate repair due to potential safety concerns. These concerns include possible trip and fall hazards. There is also a chipped and cracked step face on the central section of stairway # 2 that also requires repair due to the potential of trip hazards. Possible mold stains are present on the laundry room wall by the basement staff lounge. This wall area is behind the washer and dryer. Any leaks or sources of moisture intrusion causing the stains should be repaired. This wall area should be cleaned of the stains and should be repainted with a water proof and mold resistant paint. Cleaning and repair should be done when staff are not present in the lounge. Repair ceiling leaks in cafeteria dining room above the food service line. Replace water stained ceiling tiles after the sources of the leaks have been fixed. 30.0
8. Repair and reattach loose hanging light fixtures shield covers in the central stairway with the skylight. 20.0
11. Cleaning chemicals including Clorox wipes and aerosol spray cans of Lysol disinfectant were left out in areas accessible to students in classrooms. Cleaning chemicals and aerosol products must be stored in areas only accessible to staff. Examples: Cleaning chemicals can be stored in closed or locked cabinets, desk drawers, stock rooms, or closets. 30.0
General Comments
Repair damaged roof on the gazebo on the playground.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 01/13/2021
Score: 90

#  Comments Points
3. Repair nonfunctional drinking fountain by boys and girls restrooms #208 and #209. 20.0
4. Repair leaking urinal in boys bathroom #117. 20.0
6. Replace permanently stained carpet in classroom #119 A. Repair ceiling leak in classroom #201. Replace water damaged ceiling tile after the leak is fixed. Repair major roof leak in stairway #4 at the skylight. Repair water damaged ceiling covering around the skylight after the roof leak is repaired. Repair chipped wall paint in stair way #5. Repair damaged and peeling wall paint in girls bathroom #203. Repair chipped ceiling cover in cafeteria storage room #119 C. Repair damaged porch ceiling covering over the front gated building entrance. Stairway #2 has peeling wall paint, chipped and deteriorated plaster walls, and chipped and deteriorated plaster on the base support platforms beneath the stairs. Stairwell #2 walls and stair step platforms are in need of urgent repair. The chipping plaster on the stair walls and on the step platforms is a safety concern. Chipping beneath the step platform may have damaged cement. Continued deterioration could possibly create structural integrity concerns for both the stair walls and step platform. There is also a concern of falling plaster in this stairwell. This is a repeat inspection violation item from the 2019 and 2020 facility sanitation inspection reports and has not been addressed. 30.0
7. A book case with class office files and supplies was present in class bathroom #207B. Class bathrooms are not clean storage locations. Storage of administrative and class supplies in bathrooms is an impediment to the cleaning and repair of these facilities. Please remove. 10.0
8. Repair nonfunctional ceiling light over the toilet stalls in girls bathroom #103. 20.0
General Comments
School building sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 03/13/2020
Score: 95

#  Comments Points
6. Ceiling leaks are present in the media center room #113 and in the cafeteria dining room/gym. Repair ceiling leaks A.S.A.P. Repair chipped plaster walls in the gym/cafeteria dining room. The north and south stairways #1 and #2 have peeling wall paint, chipped plaster walls, mold growth on walls, and chipped plaster on the base of stairs beneath step support platforms. These stairwell walls and step platforms are in need of urgent repair. The mold growth on walls is a concern for children and staff with respiratory health issues. The chipping plaster on walls and on step platforms is a safety concern. Chipping beneath step platforms has damaged cement and exposed support rebar. Continued deterioration could possibly create structural integrity concerns. There is also a concern of falling plaster in the stairwells. This is a repeat inspection item that was also documented in the 2019 facility sanitation inspection and has not been addressed. 30.0
8. Repair nonfunctional light fixtures in student hall bathrooms #103 and #115 20.0
General Comments
Facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 04/25/2019
Score: 93.5

#  Comments Points
4. Repair nonfunctional urinal in boys bathroom # 209. Replace damaged toilet seats in boys bathroom # 209. Replace loose floor vent cover in girls bathroom # 203. 35.0
6. Ceiling cover in stairway # 4 is peeling. Ceiling leaks are present in the multipurpose room and on the second grade 200 hallway. Repair these leaks and replace water damaged ceiling tiles. Repair chipped wall paint in multipurpose room # 19 B kitchen. On the Hinsdale street side stairwell and on stairwell #2 upper and lower levels there is chipping and peeling paint on walls, ceilings, and on the support base beneath the stairs. It appears this is the result of possible moisture damage. The damaged paint coverings of the walls, ceilings, and stair support bases is severe on the lowest levels of these stairwells. Chipping paint is also present on the original exterior door frame of stairway #2 and on the boiler room entrance on the Devereaux Street side of the building beneath the west wing stairs. 30.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 08/23/2016
Score: 91

#  Comments Points
4. Repair a hole in the ceiling in 103 ( girls bathroom ). Replace a missing ceiling tile in 115. 15.0
5. The cafeteria prep room did not have soap at the hand wash sink. 20.0
6. The moisture damaged paint in stairwell 1 and 2 was painted over during the summer, but the new paint is flaking again already. The paint in the basement custodian storage room ( washer/dryer in this room ) is flaking heavily. Moisture damage to the walls in custodian closet 105. The skylights in stairwell 4 and 5 have flaking paint. Remove the contact paper on the wall in custodian closet 205 A and replace with permanent waterproofing material like FRP. The carpet in 118 is very stained. Repair a hole in wall at the entrance to the multipurpose room. The mop sink basin tile in 209 A is completely broken and bare wood is showing. 15.0
7. The space under the book storage shelves in 201 A should be closed to avoid debris accumulation under the shelves. The space is too narrow for regular floor cleaning. The bathroom 207 B has cubbies. Bathrooms should not be used to store student belongings. 20.0
8. Dust and clean the windows and blinds as needed. 20.0
General Comments
This school does not have a permitted school cafeteria. Meals are sent from another school. Technically, you can only serve those meals or individually packaged foods. Observed teachers serving grapes and blueberries and crackers from large boxes. The classrooms do not have hand sinks. In order to serve fruit, you need to wash your hands and then wash the fruits. The fruit should also not be placed back into the shopping bags after washing. The children need to wash their hands before eating finger foods. Obtain permission to use the small prep cafeteria to wash fruit.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 09/11/2015
Score: 90.5

#  Comments Points
3. There is pink mold growth on the fountains in the 3rd and 4th grade hallway, and at the fountain near stairwell 5. Clean the fountain in 5th grade hallway. 20.0
4. Note : The bathroom floor cleaning method is causing the paint on the walls to become discolored. Repair damaged paint behind commodes in boys bathrooms as needed. 0.0
5. The hand sink in the cafeteria kitchen did not have paper towels. Clean the wall behind the soap dispenser at the 2n floor hand sink group. 0.0
6. The paint in stairwell 1 and 2 is flaking and peeling, especially in areas below ground. Wall and ceilings in the basement have extensive moisture damage. The paint in stairwells 4 and 5 is starting to flake, especially in the skylight. Repair the floor in custodian room 105. This room also has water damage around the mop sink. Repair moisture damage around sink in 205. Repair moisture damage around the window in the kindergarten classroom. Room 120 A has moisture damage to the ceiling. 15.0
7. The shelving in book storage rooms in too close to the ground. Raise the bottom shelves high enough to allow for cleaning under the shelves. Sweep storage rooms and mechanical rooms. 10.0
8. Clean the windows ( dust, spider webs ). Dust the sound barriers in 2412. 20.0
11. Chemicals like Chlorox wipes and disinfectant sprays are stored in various locations in the classrooms. Chemicals need to be stored out of reach of children. To be considered out of reach, the item needs to be stored at least 5 feet off the ground or in a locked cabinet. 30.0
General Comments
Recommendation : The classrooms do not have convenient hand sinks. Snacks should be purchased in individual portions, not large bags that need to be opened and divided among students ( opening a bag and handing out individual portions is considered food prep ). The cafeteria does not have convenient hand sinks. Install one or two hand sinks to encourage handwashing before meals.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 06/17/2014
Score: 95

#  Comments Points
4. no points - Clean walls in boys restrooms, repair broken floor tiles. 0.0
6. Walls in kindergarten/1st grade need repainting. Wall behind water fountains on 3rd/4th grade hall needs repair. Wall in kitchen at 3-compartment sink is peeling -repaint. Walls, floors and ceilings in most janitors closets are in poor repair - replace broken/missing floor tiles, repaint where paint peeling. Peeling paint very bad in stair wells, repaint. 30.0
7. No storage allowed in restrooms. Books stored in special ed. class. Clean out storage areas in basement. Storage on floor. Clean storage rooms downstairs. 20.0
8. no points - Clean air vents in classrooms 0.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

PARTNERSHIP ELEMENTARY SCHOOL
Location: 601 DEVEREUX ST RALEIGH, NC 27605
Facility Type: Schools
Inspection Date: 12/13/2011
Score: 96

#  Comments Points
1. NEED BACK FLOW PREVENTERS ON JANITORS SINKS,CHEMICAL DISPENSERS AND WASHING MACHINE. 30.0
7. KEEP STORAGE OFF THE FLOOR TO FACILITATE CLEANING IN STORE ROOMS. 10.0
General Comments
2 WATER FOUNTAINS ON 5TH GRADE HALL NEED CLEANING, ALL OTHERS LOOK GOOD. WALLS IN BAD REPAIR IN JANITORS CLOSETS ON 5TH GRADE HALL & IST FLOOR.