One depth marker was missing "FT" and then another one was missing on the surface of the pool deck which caused there to be a spacing of greater than 25 feet between markers. Markers were fixed during the inspection, but points taken.
4.0
11.
Couple of handrails are slightly loose and should be tighten
2.0
15.
Ring buoys were longer than 50ft and were fixed during the inspection points taken but not closing.
6.0
16.
Fence is greater than 4 inches between vertical members and pool fence is grandfathered due to age of fence. Should fix damaged portion near wading pool cabana section.
4.0
28.
Garbage bins in the mens showers should be moved before use to allow for showers to be utilized during season.
2.0
31.
One of the mens toilets are not working and should be fixed.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Ladder needs tightened(complied during inspection).
0.0
24.
There are two pumps serving the recirculating system: one for the main drains and one for the skimmers(surface overflow system0.This is not approved per .25189(c) which states the circulation piping shall be designed such that flow from the pool can be simultaneous from the overflow system and the main drains. A solution for correction must be determined before operating next year.
Clean up pump room.
4.0
25.
Clean up chemical room.
2.0
26.
Draw flow arrows on piping.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Repair far left sink in men’s room...drains slowly. Remove chair storage from bathrooms.
2.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
General Comment: Both ring buoy throw ropes were 53' feet long. Ring buoy rope shall be 1.5 times the width of the widest part of the pool or 50', whichever is shorter. Ropes were trimmed during inspection
0.0
25.
Storage other than chemicals observed in the chemical room. No storage besides chemicals allowed in the chemical room. Clean out chemical room.
2.0
29.
General Comment: There appears to be a leak behind the toilet in the middle stall of the men's restroom, repair.
0.0
General Comments
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
This pool must remain closed until the local and state closure orders currently in effect as a result of the COVID-19 pandemic are terminated.
No night swimming.
Pool staff and patrons are strongly encouraged to comply with the most current CDC guidance concerning social distancing related to the COVID-19 pandemic.
Wake County Plan Review and Recreational Sanitation Section recommends pools be hyper chlorinated at least twice a month. This activity should be accurately logged on the CPO check list form.
Lifeguarded and gate attendant at all times. One maintenance page locked. *Recommend repainting depth/diving markings or change to permanent markers. No night swimming.
Fencing between the wade pool and the swimming pool is at 46 inches where there is turf. Remove turf where needed so that the fence is at 48 inches from the wade pool side.
Fencing between the wade pool and the swimming pool is at 45 inches where there is turf. Remove turf where needed so that the fence is at 48 inches from the wade pool side.
Main entrance door leading into pool enclosure did not latch properly when held approximately 1 inch open. Doors are self close and self latch.
4.0
25.
Chemical storage room is to be used for the storage of chemicals only.
2.0
General Comments
NO NIGHTIME SWIMMING ALLOWED. Permit will not be provided to facility until both Wake County CPO and National CPO documentation provided for Kristine Minton to Andrea Anover by end of day.
Pump room ventilation fan is not working. Room also has cross draft ventilation but it vents onto pool deck area. Wake county rules do not allow for ventilation onto deck area. Repair.
2.0
General Comments
Pool is lifeguarded during all hours of operation.
Stops ringing after 3 rings. Have fixed to continuously ring prior to pool opening on May 8, 2010. Call Jason Royal @ 919-868-2562 to visit and verify phone prior to opening.
Pool chlorine level was 0.5 P.P.M. Minimum level of 1.0 P.P.M. of chlorine is required disinfectant level for pool.
6.0
8.
Replace missing weirs in pool skimmers.
4.0
General Comments
Pool permit not issued due to chlorine level. Call 868-9245 to schedule a reinspection for permit. Swim club pool must remain closed to public until permit is issued.