Facility



North Garner Middle School


720 POWELL DR
GARNER, NC 27529-3128

Facility Type: Schools
 

Related Reports

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 03/23/2021
Score: 90

#  Comments Points
4. All the urinals in the following facility boys bathrooms lack adequate water pressure and require repair: in the auditorium boys bathroom, in boys bathroom #1216A, in boys bathroom #1615, in boys bathroom #1603, in boys bathroom #1508, in the seventh grade wing upper and lower level boys bathrooms, in boys bathroom #1401, in boys locker room bathroom #1707, in the gym lobby boys bathroom #1703, and in the field house boys bathroom #1905. Repair toilets with low water pressure in the following school bathrooms: in both the boys and girls auditorium hall bathrooms, in the second stall of cafeteria hall girls bathroom by room #1233, in the end stall of the girls bathroom #1616, in boys bathroom #1401, and in the media center girls bathroom #803. Repair the leaking toilets in the following school bathrooms: in boys bathroom #1603, in girls locker room bathroom #1708, in the first stall of the gym lobby girls bathroom #1701, and in the second stall of the cafeteria hall girls bathroom at room #1233. Repair or replace toilet that has a leaking and cracked rim in the cafeteria hall boys bathroom by room #1233. Repair nonfunctional toilets in girls hall bathroom #1411 and in the girls locker room bathroom #1708. Replace missing seat on toilet in dressing room bathroom #1111A. Replace two broken toilet seats in girls bathroom #2310. 40.0
5. Repair nonfunctional hand wash sink faucets in the following school bathrooms: dressing room bathrooms #1111A and #1109A, boys bathroom #1603, boys locker room bathroom #1707, girls locker room bathroom #1708, and in the boys fieldhouse bathroom #1905. Repair leaking hand wash sink in staff bathroom #1303. This leak is on the plumbing beneath this sink. 30.0
6. Repair roof and ceiling leaks in the following school building locations: in the auditorium, in the lighting booth of the auditorium, in the hallway outside of the office and auditorium, on the 1100/band hallway, in the hallway at staff bathroom #1407, in the hallway at classroom #1313, in the special needs classroom #1310, in the hallway at boys bathroom #2307, in the gym/athletic department laundry room #1712, and in the gym concession stand #1702. Replace water stained ceiling tiles after the sources of these roof and ceiling leaks have been fixed. Replace water damaged floor tiles in the gym laundry room #1712 and in the basement area. Repair cracked and chipping plaster ceiling in the basement. Basement floors require cleaning of mud residue caused by flooding. Replace damaged and missing floor tiles at the top entrance to the stairs to the sixth grade hallway. (Trip hazard) Reattach loose base tile also on the stairs to the sixth grade hall. (Trip hazard) Reattach loose wall base tiles throughout the length of the walkway ramp on the seventh grade lower level. (Trip hazard) 30.0
General Comments
Replace missing paper towel dispenser in boys locker room bathroom #1707. There is a strong sewer gas odor in the fieldhouse boys bathroom #1905. The floor drains in this bathroom should have water poured into the drains regularly by cleaning staff. When the floor drains have dried out the empty pipes provide an access/entry point for sewer gas into the bathroom. Please address. The basement area is flooding frequently during heavy rainfall. The basement is in need of a sump pump and a drainage system is needed in the adjacent earthen crawl space. These mitigations are needed to prevent the saturation of the crawl space soil and the flooding of the basement. Repairs are also needed to prevent the possible deterioration of the building foundation in this location and to prevent mold growth in the basement. School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 03/02/2020
Score: 88.5

#  Comments Points
3. Repair nonfunctional drinking fountains in special needs classroom #1310 and in the hallway by the gym boys locker room # 1707. 20.0
4. Repair nonfunctional toilets in the girls office hallway bathroom, (four toilets), boys office hallway bathroom, (one toilet), Girls 1300 hallway bathroom #1316 (one toilet), Girls hallway bathroom #2310, (One toilet), Girls bathroom #1514, (Two toilets), boys bathroom #1419 (one toilet) girls bathroom in the 1400 cafeteria hall (one toilet) Girls 1200 hall bathroom, (one toilet), and in the girls locker room bathroom #1708, (One toilet), (Thirteen total toilets are nonfunctional and require repair A.S.A.P.) Student bathrooms and bathroom fixtures on the 1600 hall have build up and residue and are in need of better cleaning. Replace broken toilet seats in girls bathroom # 2310 and in boys bathroom #1419. Repair broken bathroom toilet stall doors in the boys bathroom # 2307, and in the boys locker room bathroom #1707. Replace missing bathroom wall tiles in boys bathroom # 1216. 35.0
5. Repair nonfunctional hand wash sinks in the girls bathroom in the main office hall, in the girls media center bathroom #803, in the boys hall bathroom #1508, in girls hall bathroom #1616, and in the 1200 hall boys bathroom. (Five total student bathroom hand wash sinks are nonfunctional.) Repair is needed A.S.A.P. 15.0
6. Repair ceiling leak in media center office #812. Repair loose stair tread on stairs leading to 2300 hallway entrance. (Priority repair. Trip Hazard) 15.0
8. Replace missing ceiling light shield cover in the boys 1200 hall bathroom. 20.0
11. Cockroaches have been spotted in special needs classrooms, bathrooms, and kitchen. Rooms #1308, *1309, and #1310. Professional pest control treatments are needed. 10.0
General Comments
Facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 07/27/2017
Score: 89

#  Comments Points
4. Two commodes in 1616 are not working. Two urinals in the boys locker room are not working. 20.0
5. Boys bathroom 1315 has two hand sink faucets with sensors. Neither one of the sensors could be activated. They may need to be replaced. There may not be a functioning hand sink in this bathroom at this time. One of the faucets at the hand sink of the girls bathroom next to 1315 was torn out. Repair the faucet. 15.0
6. The carpet in the majority of classrooms is stained and may need to be replaced. Room 1513 smells musky. Recommend removing the carpet. Repair damaged wall corners in 1618. The paint on the back door of room 1502 is very flaky. The glass exit door next to room 1713 is heavily damaged and covered by a wooden panel. Repair the door ( the building could be entered by simply lifting the wooden panel ). 15.0
7. One of the metals panels on a set of lockers in the 1600 hallway has come loose. Debris is building up behind the panel. 10.0
8. The flat light fixtures in the media center have dust and dead insect accumulation. Clean the fixtures. The stage curtains are stained and need to be cleaned. The base of the metal panels under the windows needs cleaning in almost all classrooms. Lots of dust and spider webs build up along the base. 20.0
9. Both locker rooms need cleaning. 20.0
11. Found mouse droppings in the cabinets in 1413. Live small roach in the boys locker rooms. Note : Teachers have numerous types of cleaning chemiclas and disinfectants sitting on the tables. Once the students return on Monday, all chemicals must be stored or in a locked cabinet or in a cabinet 5 feet off the ground. 10.0
General Comments
Note about food sales at concession stands : Only individually packaged foods can be sold. If you open a food package, you need a permit. You may heat individually packaged items like corn dogs, but you cannot open the wrapper.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 07/17/2015
Score: 92

#  Comments Points
1. Commnent: C) In the 1300 hall custodial closet, the mop sink vacuum breaker is rusty and may not be functioning properly; have vacuum breaker replaced. When using mop sink faucets that have hoses and dispensers attached, make sure the water is turned off after use to prevent damage to the vacuum breakers from constant pressure. 0.0
3. Comment: Adjust the pressure on the fountains by the 1600 hall exit to the gym. 0.0
4. B) Clean and/or repair the toilets with plastic bags over them in the 1300 and 2300 hall girls' bathrooms. Repair or replace the out of order urinal and reset the toilet in the handicapped stall in the boys' locker room. 20.0
5. A) The handsink stations in the 1300 hall boys' bathroom and 2300 girls' bathrooms need to be repaired or replaced, the counter tops on the top of the sink stations are loose in both bathrooms and the faucet assembly is loose in the boys'. Replace the missing faucet aerators on 2 sinks in the 1500 hall boys' bathroom. The faucet on the middle sink in the 1500 hall girls' bathroom is not working, repair or replace. 15.0
6. The linoleum flooring throughout the school needs to be cleaned and/or stripped and waxed. The carpeting in the majority of the classrooms in the school needs cleaning. Replace the moisture damaged ceiling tile in room 2301. Repair the peeling paint in the outside breezeways. 15.0
7. A) The gym storage closets need to be cleaned out and organized, shelving or rolling dollies/carts may be needed. Old/unused or damaged equipment needs to be removed. B) There is storage on the floor in the gym storage closets, auditorium stage storage, and the special needs classroom bathrooms; storage must be at least 15 inches above the floor or arranged in a manner that facilitates cleaning or is easily moveable. 20.0
8. Comment: Room 1418 has a strong mildew smell and the AC unit filters are very dusty, change or clean filters; there were no obvious leaks at the time of inspection but this room needs to be monitored for moisture. 0.0
9. Comment: A) Replace the cover on the light in the girls' locker room shower stall. 0.0
11. B) Rodent droppings were observed in the boys' side gym storage closet, clean out this area and monitor for rodents. A live roach was found in the boys' locker room, treat this area. 10.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 06/26/2014
Score: 93

#  Comments Points
4. Urinal flush valves broken, 1200 boys, 2300 boys 20.0
6. Stair treads cracked and loose, ramp treads loose. Paint hand rails, stairs and outside. Peeling paint outdoor breezeway, hall base moldings paint 7th grade hall 30.0
9. Fix shower valves, mens 214 20.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 04/27/2012
Score: 92

#  Comments Points
3. All drinking founatin mouth pieces need cleaning. Adjust the water pressure at the fountain in the chorus room, the fountain outside of room 1303, and one of the fountains on the way to the cafeteria. One fountain near the cafeteria on 1200 hall has a small leak ( water runs constantly ). 20.0
5. The hand sink faucet in the boys bathroom in the library is corroded. Replace the faucet. 15.0
6. Paint is flaking off the metal beams and doors. The carpet is many classrooms is stained. The floors need more attention in harder-to-clean areas like the corners around lockers. Dust and debris are building up. Clean the floors around the cooking equipment in the small kitchen in the 2 story building. 15.0
8. Dust is building up on the duct work in the gym, the stage curtains, and the stage lighting fixtures ( and other high fixtures in the auditorium ). Clean the windows including the space above the windows ( spider webs; dust and dead insects on the windows and blinds ). The HVAC unit in 1429 is leaking. 20.0
11. Saw a number of large roaches in the gym storage room and trailer 4. Saw drain flies in the girls locker room. Note : Windows that are being used for ventilation should be screened to keep insects from entering the building. 10.0
General Comments
GC # 7 : The shelving in most storage rooms is only about 2 inches above ground level. This allows for debris to accumulate under the shelves, but it is not high to allow for floor cleaning under the shelves. Raise the bottom shelves or block the open space under the bottom shelf. Sand and paint the storage shelf in 1602.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 10/29/2010
Score: 90.5

#  Comments Points
4. Base tiles, floors around toilets and walls soiled in gang restrooms and staff restroom. Clean 15.0
6. Repair chipped paint in hallways, clean walls around water fountains. Clean floiors, walls, ceilings in janitor closets. Hole in ceiling tiles, water damaged in closet 1510. Stairs in six grade hallway, rubber is coming off stairs, this is a trip hazard, repair. Ramp out at trailer 2 is in poor repair. Clean janitors closet by auditorium, floors, walls, ceiling where something has splashed/sprayed all over room. 30.0
7. Storage closets have items store on floors, that prohibits cleaning. Provide shelves were needed. Clean teachers lounge microwaves. Clean refrigerator in concession stand, clean classroom microwaves. 20.0
11. Keep janitors closets locked. Closets contain chemicals that must be locked and inaccessible to students. 30.0
General Comments
Clean windows, blinds. Home economics refrigerator needs thermometer. Provide mop rack for janitors closets. Repair water faucets in 1412.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 05/08/2007
Score: 92

#  Comments Points
5. Replace broken soap dispenser in boys restroom (1600 hall). 15.0
6. Replace/repair rubber matting on rear ramp near 1600 hall. Nail heads are protruding up on one and matting is a trip hazard on the other. 15.0
8. Clean vent covers in restrooms and hallways as needed. Replace blown light bulb in fixture located in the girls upstairs restroom (2300 hall). 20.0
11. Found Goof Off chemical, which is extremely toxic, and All Purpose Cleaner in Rm 1613. Found All Purpose Cleaner in Trailer 1. Strong chemicals which are labeled `Keep Out of Reach of Children` should be stored in locked cabinets if kept in classrooms. 30.0
General Comments
Need a thermometer in Special Needs class refrigerator since this is where the students' milk is stored. Inform teachers to store chemicals in their cabinets w/ locks.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 12/21/2004
Score: 91.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 01/25/2002
Score: 96

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

North Garner Middle School
Location: 720 POWELL DR GARNER, NC 27529-3128
Facility Type: Schools
Inspection Date: 06/20/2000
Score: 88.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment