Facility



Wendell Elem. School


3355 WENDELL BLVD
WENDELL, NC 27591-7289
Phone: 919.365.2660

Facility Type: Schools
 

Related Reports

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 05/31/2024
Score: 90

#  Comments Points
3. Repair drinking fountain that has a clogged and backed up drain pipe on the top floor hallway at room #247. 20.0
4. Repair chipping and peeling wall coverings behind toilets in the auditorium building boy`s and girl`s bathrooms #102 and #103. 15.0
5. Repair clogged sink drain in the stage office of the auditorium. This sink is backed up and has standing water in it. Repair plumbing leak beneath counter top sink in classroom #243. 15.0
6. Repair loose step boards on the rear deck entry for trailer #1. Priority repairs are needed to prevent trip and fall hazards. Repair ceiling/roof leaks in the gym, over the auditorium stage, in the cafeteria dining room by the windows, in the top floor of the media center room #217, in the ground floor hall by the interior windows of the media center on corridor #154, and in the ground floor hallway adjacent to the entrance of stairway #1. Replace water stained ceiling tiles in the hallways, dining room, and media center after the sources of these leaks have been fixed. Repair chipping ceiling surfaces caused by ceiling/roof leak water damage over the auditorium stage. The auditorium is flooding frequently during heavy rainfall at the front entrance and at the lower side exit at the base of the exterior steps. Heavy rainfall runoff from the roof and parking lot should be diverted away from the auditorium building foundation. Examples: Gutters, downspouts, and downspout extensions for the roof runoff and drainage ditches or berms for runoff from the parking lot. These repairs are needed to prevent water damage and possible mold growth on the auditorium walls and floors from repeated flooding. 15.0
8. The air conditioning systems are functioning poorly in classrooms: #133, #137, #139, #201, #203, #207. These rooms lacked adequate cool air flow needed for the comfort and health of students and staff. Priority repairs are necessary. 20.0
11. Remove or replace broken bolt plates from the 3-5 playground equipment posts that are adjacent to the monkey bars and balance beams. These broken bolt plates have sharp metal edges and could be a possible injury hazard. 15.0
General Comments
School facility sanitation completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 04/12/2021
Score: 88.5

#  Comments Points
4. Repair toilets and urinals in the following school bathrooms. Special needs class bathrooms #103A and #105A. These toilets have poor water flow and are partially clogged. The main office health room bathroom toilet also has poor water flow and is partially clogged. The toilet in the principals office bathroom #119B is partially clogged and has low water flow. The toilets in both the men`s and women`s staff bathrooms #123 and #125 are clogging and require repair. Repair partially clogged urinals in the boys classroom bathrooms #137B, #143B, and #145B. Repair clogged toilet in the auditorium girls bathroom #102. Repair nonfunctional toilets in the boys hall bathroom #212 and #202. Repair clogged urinals in the men`s staff bathroom #229A. Priority repair is needed on the school building sewer lines to allow all toilets and urinals to drain and flow properly. 40.0
5. Repair nonfunctional sink in the art class kiln room #101A. Repair clogged sink in the office/staff kitchen #127. Repair clogged hand wash sink drains in the mens and womens staff bathrooms #123 and #125. Repair clogged hand wash sinks in class bathroom wet areas #129A, #135A, #137A, and #143B. Repair clogged sinks in classroom wet area #243A and in the staff work room/kitchen #229A. Priority repair is needed on the school building sewer lines to allow sinks to drain properly. Repair nonfunctional hand wash sink in the girls bathroom #206. 15.0
6. Wall paper throughout the main school building in classrooms, class bathrooms, hallways, and stairways is deteriorated, stained, torn, and peeling. Removal of wall paper, replacement of wall paper, or repainting of walls after the paper is removed is necessary. The wall paper in the main stairway/lobby is especially deteriorated and is peeling at the ceiling. Please repair. Repair roof leaks over the auditorium stage. (Building #300) Replace splintered wooden ceiling boards in the gym. (Building #400). The gym ceiling paint is also chipping and in need of repair. Repair chipping plaster walls in the auditorium boys bathroom #103. Repair major roof leaks throughout the entire length of the top floor corridor #254 and in the media center room loft #217. The worst of the ceiling leaks are concentrated at the top of the main stairs on corridor #254 at the magnet museum area. Major ceiling leaks are also present in the cafeteria dining room in building #101. The sources of all the roof and ceiling leaks should be repaired and then the water damaged ceiling tiles should be replaced. Repair the source of ceiling leaks in the special needs class bathroom #103A and then replace water stained ceiling tiles. Replace permanently stained floor tiles also in the special needs class bathroom #103A. 30.0
8. Ceiling exhaust fans in all of the student classroom bathrooms are nonfunctional and in need of repair. The air conditioning system in the auditorium and on the top floor of the main school building was functioning inconsistently. These areas did not seem to have proper air conditioning air flow and circulation and the system should be checked and repaired. Dead cockroaches were present in light fixtures in the media center loft. (Room #217). These light fixtures should be cleaned. 20.0
11. Dead cockroaches were present in light fixtures in the media center loft. (Room #217) Professional pest control treatments are necessary throughout all of the school buildings to reduce the presence of insect pests. 10.0
General Comments
The lower metal corner of the window ledge by the art class room #101 rear exit door is very sharp. This piece of sharp metal should be capped over to prevent student injury hazards. School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 08/07/2019
Score: 90.5

#  Comments Points
3. Repair nonfunctional drinking fountain in corridor # 251. 20.0
4. Repair peeling ceiling paint in auditorium boys bathroom #103. Repair nonfunctional urinal in boys classroom bathroom # 145. This urinal has low water flow. Repair broken ceiling grid in girls classroom bathroom #137C. Repair ceiling leak in girls classroom bathroom #145C. Reattach loose wall base tile in classroom # 107 student bathroom. 35.0
6. Wall paper in classroom #141 is stained and requires replacement. Repair peeling wall paint in auditorium lobby. Wall paper in student classroom kitchen # 105 is stained and peeling and requires replacement. Wall paper in corridors #156 and #157 is peeling and requires repair. Replace stained and peeling wall paper in classroom # 107. Wall paper in second floor hallway across from student restroom # 208 is peeling and requires repair. Repair ceiling/roof leaks in cafeteria dining room. Repair ceiling/roof leaks on the second floor hallways outside of girls restroom # 206, and in corridor #254. Repair ceiling/roof leaks on the second floor of the media center at room #217A. Repair ceiling leak in teachers lounge #219. Replace water damaged ceiling tiles after the roof leaks are repaired. Repair roof leak in gym and repair damaged gym ceiling areas caused by the leaks. (Priority repair due to deterioration of some parts of the gym ceiling caused by the leaks.) Repair roof leaks over auditorium stage. 30.0
7. File cabinets stored in classroom bathrooms #103 and #105 are an impediment to the cleaning and maintenance of these facilities. Bathrooms are also not clean storage locations. 10.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 08/25/2017
Score: 92.5

#  Comments Points
4. Increase water pressure at the hand washing sinks located in the boys bathroom of the 5th grade upstairs hallway, and hand sink in the bathroom associated with the auditorium. 30.0
6. Replace the peeling wall paper in the classrooms and hallways throughout the school. Replace/repair moist damaged ceiling tiles in the gymnasium. All of the facility is to be in good repair and easily cleanable. 30.0
11. Outside playground area contains badly damaged flooring. Damaged flooring could propose as a trip hazard to any child playing in this area. Have this area repaired. Rid outside auditorium vents of birds. 15.0
General Comments
Keep all hand sanitizer out of the reach of children.
Inspector contact info: Dimitri Parker (919)868-2562
* Notice* Effective January 1, 2019, the NC Food Code 3-501-16 (A)(2)(ii) requires equipment to be upgraded or replaced to maintain food at a temperature of 41 degrees F or less. Please plan accordingly.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 11/25/2015
Score: 93.5

#  Comments Points
3. Turn up the water pressure on the water fountain near the media center. 20.0
4. Clean the floors and walls in the restrooms and around the sinks. All ceiling titles must be nonabsorbent, washable and in good repair. 15.0
6. Replace the peeling wall paper in the classrooms and hallways throughout the school. Clean the carpets in the classrooms throughout the school. Replace the rusty metal rails in between the ceiling covers. The wall paper is really peeling in the following rooms 111 around the hand sink area, room 131, 212, and 241. 30.0
General Comments
8. Clean out the light fixtures to remove some dead bugs.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 07/25/2013
Score: 92.5

#  Comments Points
4. B. In several restrooms the stalls are rusty around the bottom of the stalls. In several restroom the faucets on the hand sinks are pitted. (C) Clean the floors in the restroom especially around the baseboards. 35.0
6. Replaced the peeling wall paper in the classrooms and hallways throughout the school. Clean the carpets in the classrooms throughout the school. In the classrooms 203 &207 replace the missing shoe-molding. In the same classrooms reattach the peeling shoe-molding. The floors in these classrooms have damaged floor title. Replace the stained ceiling titles throughout the school. There is a leak in the computer room. There is a garbage can to catch the water from the leak. In the computer lab there was missing ceiling title. Replace the rusty metal rails in between the ceiling titles. Some carpet is worn and need to be replaced. 30.0
7. Keep storage 15 inches above the floor in the storage and custodian's closets to facilitate cleaning. 10.0
General Comments
GC. Clean the light fixtures to remove the dead bugs.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 10/13/2011
Score: 92.5

#  Comments Points
3. Regulate drinking fountains to 45 degrees. 3/10 need regulating. 20.0
4. Grout tile as needed corners and stalls (2nd floor) Floors detail clean corners. 0.0
5. Fix or replace about 50% lvatory fixtures dripping or leaking or low flow. 15.0
8. Lighting through entire school. Clean or replace lenses. Replace all lamps (80% dm or flickering) Inadequate air filtration in trailers. 40.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 06/22/2009
Score: 93.5

#  Comments Points
4. the ceiling tiles in all bathrooms, including the smaller ones in classrooms and teacher restrooms, need to be washable; the oys and girls rooms in the auditorium have flaking paint; mineral deposits on faucet and commode in bathroom in 111 15.0
6. the carpet has some stains and fraying areas; the wall paper, especially in the lower parts of the walls, shows definite signs of aging; wall paper is yellowed, stained, and curling up at corners; the auditorium and the gym ceiling are starting to have a few loose paint flakes; the brown paint on the outside of the gym building is flaking; the base coving is damaged or loose in a lot of areas ( especially under fountains and on the wall between the bathrooms in the classrooms ); the floor seams in trailer 1 and 2 are exposed; replace stained ceiling tiles in the trailers 30.0
8. the cafeteria windows have flaking paint and rusty spots; clean the stage curtains; clean windows, window sills, and blinds; clean the ceiling vents and light shields in the library 20.0
General Comments
GC # 5 : a lot of sink basins have rusty drains and rusty cracks in the enamel; repair the faucet on the left sink in 147
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 02/04/2008
Score: 95

#  Comments Points
4. the ceiling tiles in all bathrooms, including the smaller ones in classrooms and teacher restrooms, need to be washable 15.0
6. replace moldy ceiling tile in stairway 5; the carpet has some stains; the wall paper, especially in the lower parts of the walls, shows definite signs of aging; wall paper is curling up at corners; replace stained ceiling tiles in 201 and stairway 1; the paint on the gym ceiling is starting to crack 15.0
8. ceiling vent covers and light shields have rust and mildew spots in trailer 2; replace broken light bulbs 20.0
General Comments
GC # 7 : storage room 219 A need racks or pallets to store al items 12 inches off the ground;
one the second floor, many classes run out of space for bookbags and coats, and coats and bags end up in one large pile on the floor ;
GC # 11 : please remind teachers NOT to store chemicals under the sinks; chemicals, including cleaning agents and Chlorox wipes, need to be stored 5 feet or higher or in a locked cabinet
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 08/17/2006
Score: 93

#  Comments Points
3. adjust fountains ( water pressure too low ) 20.0
4. all ceilings in bathrooms need to be washable ( no acoustic tile ); repaint or clean ceilings where needed 15.0
6. replace stained ceiling tiles; carpets are starting to show signs of wear; a few areas around windows have minor moisture damage to wall paper 15.0
8. mold spots on vents and musky odor in trailer labeled 7; clean light shields in 143 20.0
General Comments
GC # 5 : replace one faucet in 135
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 06/22/2004
Score: 95

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 05/28/2003
Score: 95.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Wendell Elem. School
Location: 3355 WENDELL BLVD WENDELL, NC 27591-7289
Facility Type: Schools
Inspection Date: 10/26/2001
Score: 95.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment