Facility



East Wake High School Building


5117 Rolesville Rd
WENDELL, NC 27591

Facility Type: Schools
 

Related Reports

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 06/28/2021
Score: 93

#  Comments Points
4. Sediment and residue build up was present in unused toilets that have been closed off for social distancing in boys bathroom #1212 and girls bathroom #1517. These unused bathroom toilet fixtures still require regular cleaning and flushing by custodial staff. Repair nonfunctional urinal in boys bathroom #1212. Repair three nonfunctional urinals that have poor water flow and poor drainage in boys bathroom #164. Repair leaking toilet in the second stall of girls bathroom #2521. 20.0
5. Repair nonfunctional water flow activation sensor on hand wash sink faucet in girls bathroom #134. Replace missing lower covering for hand wash sink basin plumbing controls and flex pipe in girls bathroom #165. Repair nonfunctional hand wash sink faucet in girls bathroom #2521. 15.0
6. Repair roof leak by the windows in the media center # 1224. Repair ceiling leak in athletic program hallway at boys locker room #182. Repair broken floor tile at the main gym entry #G-25. Repair ceiling leak and chipping ceiling cover caused by this leak in boys locker room #G-03. Repair ceiling leak at the entrance to the 100 hallway. Repaint permanently stained areas of the ceiling in boys bathroom #1519. Repair ceiling leak in special needs class bathroom #2527A. Water damaged ceiling tiles in all of the listed leak areas should be replaced after the sources of these leaks have been repaired. Repair loose floor wiring for walkway border lights adjacent to seats in the auditorium. This loose floor wiring is a trip hazard and should be repaired A.S.A.P. 15.0
8. Repair nonfunctional air conditioning systems in the athletic program hallway by the boys and girls locker rooms #182 and #183, in the gym hall by rooms #176 and #177, and in the hall adjacent to the boys locker room entrance #G-07. Repair nonfunctional air conditioning system inside of the boys locker room #G-03. (Priority repair) The air conditioning system is completely nonfunctional inside of this boys locker room. Replace missing ceiling light shield in boys locker room bathroom #G-03. Repair nonfunctional ceiling light in girls bathroom #2217. 20.0
General Comments
Emergency changes of clothing for students in the special needs class bathrooms #2527A and #2527B should be kept in plastic bins with lids to keep clothing items clean and free of contaminants. Items including a drink cooler and class chairs and desks were stored in the special needs class bathroom #2527A. Class bathrooms are not clean storage spaces. Only items related to bathroom use should be kept in the special needs class restrooms. A bottle of cleaning chemical was left in the special needs class bathroom #2527B in an area accessible to students. Cleaning chemicals and aerosol sprays should be stored in areas only accessible to staff for use. Example: Cleaning chemicals should be stored in closed or locked cabinets or supply closets. Toilets and urinals closed for social distancing in student restrooms should be flushed and cleaned at least weekly by custodial staff to prevent, odors, drain flies, and residue buildup. Repair broken water control valve in one shower in the boys locker room #183. Repair two nonfunctional showers in the boys locker room #G-07. One shower has a loose spray nozzle and the other shower has poor water flow. School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 06/13/2018
Score: 92

#  Comments Points
3. Drinking fountains in 2300 hallway as well as 2200 hallway contain pink mold around spout. Drinking fountains shall be clean and in good repair. 20.0
5. Sink handle for hot water in restrooms on 2200 hall in bad repair and not dispensing hot water. All lavatory fixtures shall be clean and in good repair. 15.0
6. Carpet in several classrooms were stained. Walls throughout contained chipped paint. All floors, walls, and ceilings shall be clean and in good repair. 15.0
9. Shower fixtures in all locker rooms are soiled. Brown sludge coming out of faucet in girl`s locker room and inside sink. Shower curtains in all locker rooms need cleaning/replacing. 30.0
General Comments
Inspector information: Kaitlyn Yow, Kaitlyn.yow@wakegov.com
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 06/15/2016
Score: 94

#  Comments Points
3. (B) The water pressure was low on the water fountain near the restroom 264 0.0
5. The toilet seats in restrooms 134, 135, 165 need to be replaced. The toilet seats have several burn marks on the seats. All equipment must be in good repair and easy to clean. 15.0
6. The walls in the hallway near the transportation area needs to be repainted. The floors need to be waxed in room 154 and in the modular classrooms 11 and 12. In room 1208 the walls need to be repainted. 15.0
8. Clean the vents in restrooms # 134, 135, 164. Replace the torn blind in room 1207 0.0
9. B. Clean the showers in the locker room 183 and 184. Replace the moldy shower curtains. (C) Clean the locker room to remove the food boxes and chip bags and soft drink bottles. 30.0
11. Cut the grass around the modular classrooms. 0.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 06/30/2014
Score: 93

#  Comments Points
3. Detail clean fountains, about 1/2 need regulated 20.0
5. Fix all metered faucets 316, not working properly 15.0
6. All exterior steel doors need paint and canopy has rust and peeling paint. 15.0
8. Clean air handler coils, room 1501 20.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 02/21/2012
Score: 92

#  Comments Points
3. Clean the black build-up off of the water fountain spots located in the 1200's hallway and auxillary gym hallway. There were also some water fountains that were corroding and no longer in good repair, located at the main lobby restroom area. 20.0
5. Replace the cracked hand sink basin in 135. One hand sink, in restroom 135, was not working. One hand sink was not working at the 2221 boys restroom. Loose faucet found at a hand sink in boys restroom 2221. Must be in good repair. 15.0
6. Clean the paint off of the floor in the main boy's locker room. Replace the cracked floor tiles in secondary weight room, 174. Floor and ceiling damage in trailer #2. Cracked corner walls in rm2216 and another computer room. Tearing in the carpet, in the library. Must be in good repair. Clean the ceiling in the boys restroom, 2221. 15.0
7. Storage was found on the floor in 1311A, 2nd floor storage room, 1209A, and computer storage room 1224. Storage is to be at least 15 inches off of the floor to help facilitate cleaning. 10.0
8. Replace damaged blinds in rooms 242 and 159. Clean the dust build-up on the ventilation units located in rooms 1317, 1313, 1526, and 1528. Replace the blown light bulbs in the boys main locker room, 1313, 256, and 180's hallway. Clean the dead bugs out of the light shields closest to the front doors. Clean the vents in the auxillary gym. 20.0
General Comments
4. Replace the worn/stained toilet seats in the main lobby restroom.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 08/20/2009
Score: 95

#  Comments Points
5. replace the cracked hand sink basin in 135; one faucet in 1517 does not work 15.0
6. the ceiling in the large gym has some damage ( torn plastic ); clean ducts and ledges in the gyms 15.0
9. replace the shower curtains in the boys team locker; one hand sink faucet in the girls locker room does not work; the largest boys locker room does not have air conditioning and the odor is very, very strong; two shower heads in this locker room are leaking; paint the ceiling in G03 20.0
General Comments
GC # 8 : no AC on the old science hall ; clean high vent covers ( as in the band room , for example ) ;
GC # 4 : paint the ceiling in 1303 and 2301;
GC # 6 : the carpet in several trailers is showing signs of aging ( wrinkles, stains, torn spots ); sweep the electrical rooms
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 02/19/2008
Score: 95

#  Comments Points
5. the very left faucet at the hand sink in girls team locker does not work; replace cracked sink in 135; one faucet in mens room near 2525 does not work 15.0
6. the carpet in trailers T1 and T5 has some stains, and the carpet in T2 is very wrinkled; repair a hole in wall in G07; one stage dressing room floor needs to be cleaned; clean duct work in the auxilliary gym and high ledges in gym and lobby; floors and walls in the weight room need repair and paint; several of the foam panels at the gym ceiling are torn; there are numerous cracked floor tiles, a crack in the outer wall of the building ,and a wet ceiling tile near the entrance to the gym; repair broken tiles in 135 15.0
9. pink build-up on shower walls and shower curtains in boys team locker rooms; repair leaking shower in G07 20.0
General Comments
GC # 8 : several egress windows have moisture between the window panels ( see rooms 242 and 244, for example ); one vent in the media center has spider webs hanging from it; dead insects in the light shield in 134 ;
GC # 7 : clean the custodian closet near the main office; room 1515 E needs storage racks
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 08/15/2006
Score: 91

#  Comments Points
4. recaulk commodes where needed; sink in 135 is cracked; smaller bathrooms ( mostly inside classrooms ) need washable ceilings ( no acoustic tile ); bathrooms in South Hall need thorough cleaning 35.0
6. carpets in older parts of the building are in bad shape; replace stained ceiling tiles in Siemens hall ( and a few throughout the facility ); a lot of missing or damaged baseboards; clean and paint walls as needed; repair floors in 121/122 15.0
8. dust vent covers in older part of the building; clean light shields; one broken light shield in girl`s locker; repair blinds in 100 20.0
9. major odor problem in boy`s locker room; needs additional ventilation and A/C and more frequent washing of clothing; clean walls and ceilings 10.0
11. numerous flies in boy`s locker room; roaches in 128 10.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 06/01/2004
Score: 97

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

East Wake High School Building
Location: 5117 Rolesville Rd WENDELL, NC 27591
Facility Type: Schools
Inspection Date: 11/01/2001
Score: 94

#  Comments Points
General Comments
Red Denotes Critical Violation