Ligon Middle School


706 E LENOIR ST
RALEIGH, NC 27601-2029

Facility Type: Schools
 

Related Reports

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 06/12/2023
Score: 89.5

#  Comments Points
3. Repair water fountain that is leaking onto the floor beneath it. This fountain is located in the hallway beside the boy`s hall bathroom #2314. Repair nonfunctional water fountain in the hallway beside dance studio classroom #6107. 20.0
4. Repair toilet in media center bathroom #4212A. This toilet has poor water flow for flushing. Repair urinal and toilet in boy`s hall bathroom #3209. Both bathroom fixtures are nonfunctional due to plumbing pipework leaks. Repair two toilets in the girl`s gym hallway bathroom #7102. Both toilets have poor water flow for flushing. Repair ceiling leaks present in the girl`s gym hall bathroom #7102. The ceiling in this bathroom has water damage and a hole in it. Replace the water damaged section of bathroom ceiling after the leak is fixed. Repair nonfunctional toilet in the gym hallway boy`s bathroom #7104. Repair nonfunctional toilet in the end stall of boy`s bathroom #3111. Repair broken toilet stall door in the cafeteria hallway boy`s bathroom #5101. This toilet stall door is difficult to open. Repair toilet that has a broken ceramic base in the girl`s hall bathroom #1230. Repair urinal that has poor water flow for flushing due to leaks in the boy`s hall bathroom #2314. Repair nonfunctional toilet in boy`s hall bathroom #1216. This toilet is nonfunctional due to poor water flow for flushing caused by leaks on the pipework at the rim of the commode. Repair ceiling leak in student services office bathroom #1201k Replace water-stained ceiling tiles in this bathroom after the leaks have been fixed. Repaint chipped wall surfaces also in bathroom #1201K behind the toilet. There is an exposed metal base left over from a removed toilet stall on the floor of boy`s bathroom #1234. This metal base is rusted with sharp edges and is in an open area of bathroom floor. This could cause trip and fall hazards as well as cuts or other injuries. This exposed metal base should be removed from the bathroom floor. 35.0
5. Reattach loose hand wash sink basins to walls in the following bathrooms: in the girl`s locker room bathroom, in the girl`s hallway bathroom #3113, and in the boy`s hallway bathroom #3111. The handwash sink basin in the girl`s locker room bathroom is hanging so loosely from the wall that water does not flow down into the drains of this sink. All three-bathroom sinks listed require priority repairs to reattach the sinks securely to the bathroom walls. Repair broken faucet on handwash sink in the cafeteria girl`s bathroom #5102. Repair two handwash sink faucets that have poor water flow in girl`s bathroom #3225. These hand sink faucets require new screens to allow for better water flow. 15.0
6. Repair ceiling leaks in the following school locations: in the art classroom #6101 both in the center of the room and adjacent to the side glass exit doors, in the auditorium costume room #6105 at ceiling vents and in the front and back corners of the room, in the media center at the sprinklers, and in stairway #S-1 on the top floor ceiling adjacent to the air conditioning unit. Replace water-stained ceiling tiles in these locations after the sources of the leaks have been fixed. Clean the roof gutters adjacent to art classroom #6101 to prevent the interior roof leaks at the glass door side exit. Repair broken hand railing on steps leading to the entrance of the auditorium. Repair broken hand railing on steps leading up the entrance of room #6103. Repair broken wooden floorboard on steps leading to entry ramp for trailer #1. Priority repair for safety is necessary to prevent trip and fall hazards. Replace deteriorated and sagging floorboards on entry ramps for trailers #1 and #2 and on the rear deck and steps of trailer #2. Priority repairs are needed to prevent potential trip and fall hazards from these loose floorboards and due to possible collapse of some deteriorated floorboards under foot. Repaint chipped and peeling wall surfaces in classrooms #1237 and #2302. 15.0
8. Repair nonfunctional vent hood over kilns for art classroom #6101. Priority repairs for health and safety are required for the vent hood in order to properly ventilate heat and dust particles out of the building when the kilns are in use. 20.0
General Comments
Repair or replace broken chair in the school auditorium at the front of the stage. Replace two missing shower heads in the boy's locker room.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 10/05/2020
Score: 91.5

#  Comments Points
4. Repair nonfunctional toilets in girls bathroom #2210,(One Toilet), in girls bathroom #3225,(Two Toilets), and in boys bathroom #3209, (One Toilet). Repair leaking toilet in the girls bathroom #3207. Repair nonfunctional urinal in boys bathroom #3111. 20.0
5. Repair broken hand wash sink faucet in staff bathroom #3202B. 15.0
6. Major roof leaks on the gym are causing the entire interior ceiling cover to collapse. Insulation is exposed in multiple locations along the gym ceiling due to the leaks. There are possible safety concerns due to materials and ceiling components possibly falling onto occupants in the gym. Roof repair and interior gym ceiling replacement is needed in the gym A.S.A.P. Walls and ceilings in mechanical room #7004 are peeling and require repainting. Repair hole in floor foundation at the main entry to the 2200 hall. (Safety hazard). Ceiling paint in custodial closet #1214 is peeling and needs repainting. Repair ceiling leak in student services staff bathroom #1201K. 30.0
8. Repair nonfunctional ceiling light fixtures in girls hall bathroom #1212 and boys bathroom #6111. 20.0
General Comments
School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 02/12/2019
Score: 87

#  Comments Points
4. Repair nonfunctional toilets in boys and girls student bathrooms # 1234, # 2210, # 3113 # 3207, # 3225, and # 7102. Toilet in girls bathroom # 3207 had major build up and residue and had not been cleaned for some time by the night crew. Repair chipped wall paint in special needs class bathroom # 3104. 35.0
5. Repair nonfunctional hand wash sink faucet in boys bathroom # 1216. Repair loose hand wash sink faucet in girls bathroom # 3113. 15.0
6. Major roof leaks on gym are causing interior ceiling cover to collapse. Roof repair and interior ceiling cover replacement is needed in gym. Repair roof and ceiling leaks in hall at stage door # 6105 and at chorus room door # 6114. Repair ceiling leak in media center entrance at sprinkler head. Repair ceiling leaks in stairwell # 2 and in stairwell # 7103. Repair ceiling leak in classroom # 1235. Repair leaks in window frames for classroom # 1238. 30.0
8. Repair nonfunctional ceiling light fixtures in girls bathroom # 1212. 20.0
9. Repair peeling ceiling paint cover in boys locker room. 15.0
11. Junk and debris on the loading dock between the media center and cafeteria should be removed from the premises to prevent pest harborage areas. 15.0
General Comments
Gutters and downspouts outside of art room # 6101 should be repaired to carry storm water runoff away from the building and to prevent repeated flooding of the art room.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 03/06/2018
Score: 91

#  Comments Points
4. In the men`s bathroom 7104 there is broken tile that has been patched but needs painting and peeling paint on the ceiling 0.0
5. in bathroom 1212 the sink is rusty on the far left, toilet seat missing in the handicap stall in bathroom 3225, The handicap stall toilet will not flush in bathroom 7102 near the gym, in bathroom 6111 the urinal is out of order and needs to be fixed. 15.0
6. In the 6th grade hallway area: fix the crackling paint in room 2208 near the ceiling on the back wall. Fix the cracked stairs in the stairwell, paint the rails in the stairwell, repaint the walls in the hallways. In the 7th grade hallway fixed the cracked plaster outside of room 3203, 3205 and outside of 3204. Also repaint the railings in the upper 7th grade hallway. Repaint the 7th grade hallways. Repaint the rusty doors in stairway S4. In the 8th grade hallway there are many rusty lockers that need to be repainted, repaint door frames in the 8th grade hallway. In the gym area: replace the bleacher slab that is missing, replace blinds, repaint door frames, repair the cracked plaster in the ceiling, repaint the iron beams in the ceiling, caulk the entrance on the side wall. Repair the ceiling tile leaks outside 7002 near the gym, repaint the wall and ceiling tiles, replace ceiling tiles outside of room 7011 toward the locker room. Fill in the missing areas on the steps and repaint railings in the 700 hall. Outside of the auditorium: replace the rubber mats on the steps that lead to the Haywood Street entrance. 15.0
7. Keep storage off the floor in room 1241 and in the shop closet. Remove unused items. 10.0
8. Blinds need replacing in rooms 2205, 2208, 3213,3216, in the gym, and in the autistic classrooms room 3102 and 3106. Vents need to be cleaned inside and outside the bathroom 1230, vent over the urinals in bathroom 1234, in room 3203, vent over the urinal in room 6111. Ceiling tiles are dusty in room 3216. Fix the cracked window in stairway S4 facing Church Street. Repair the window leak in room 1228. 20.0
9. In the boy`s locker room there are some broken and dented lockers and one locker was missing a door. 0.0
11. rooms throughout the school have hand sanitizers, Clorox wipes and other cleaning chemicals within reach of the students. Keep these items 5 ft up off the floor. Suggest sending out an email to remind teachers of this rule. 30.0
General Comments
Have the greenhouse panels repaired, buy dirt to fill in the raised beds for the agriculture project and work on discovering the cause of the bad odor in the band room. There is a ceiling leak in the library that is being fixed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 07/24/2015
Score: 89.5

#  Comments Points
4. B. Worn toilet seat in boy's restroom 1234, replace. Leaking faucet at the hand sink in the men's restroom 1501. C. Broken floor tile in the men's restroom 1216. Tile coving is broken in the girl's restroom located by the library,=. 35.0
6. Water is leaking thru the ceiling in room 3105. Standing water in the hallway by room 7010. Water damaged ceiling tiles in room 3110, 6104, in the hallway by 6110, closet 2208, and in the choir room. Ceiling tile is off the ceiling in room 3105. The gym ceiling cover is torn in several places, is water damaged, and paint chips are coming off in chunks, repair. Repeat Worn walls in room 2310 and 2208. Hole in the wall in the stair landing 1S between the 1st and 2nd floor. Stairway landing by 3102A is missing floor tile, repair. Stir tread is coming off stair in stairwell S4. Stained carpeting in rooms 3102, 2201, 2307. Custodial closet floor is dirty for closets 2309 and 1233. 15.0
7. Keep storage of the floor on shelving or in cabinets for the following closets: 2208, 1233, 3110 and shop closet. 10.0
9. B. The urinal is leaking on the floor in the boy's locker room, repair. A. Floor tile is broken in the boy's locker room. 35.0
10. B. Trash on the dumpster pad, tables and wooden pallets. 10.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 02/05/2015
Score: 91

#  Comments Points
4. A. The ceiling in the boy`s restroom number 1234 is stained and dirty. Wall is worn in boy`s restroom 2314. Tile coving is missing in boy`s restroom number 3209. 15.0
6. The gym ceiling cover is torn in several places and is water damaged, repair. Repeat. Paint is flaking off the wall in chunks in classroom 2208. Repair the worn sheet rock wall in the landing in the stairway to the 6th grade hall. Water damaged ceiling in the prop's storage closet, repair. Stained carpeting in trailers one and two. 15.0
7. A. Dirty floor in the janitor closets 1234 and 1214. B. Keep storage of the floor on shelving or in cabinets for the following closets: prop closet, art closet, the stage closet, closet 4212, custodial closet 1214, closets in trailers one and two and teacher work room 2304. 10.0
8. Blind is bent badly in room 3213, replace. Window does not close in classroom 3213, repair. 0.0
9. A. Broken floor tiles in the boy's locker room, repair. B. The faucets in the girl's locker room are not working, replace the batteries. 20.0
11. Chlorox wipes and hand sanitizer are stored in several of the classrooms accessible to children. Store out of reach of children or in closet or cabinets when not in use. Chemicals were found in classrooms stored accessible to children this includes: Febreeze, lysol cleaner, rubbing alcohol, white out, miracle grow, glade, wood glue, hydrogen peroxide and all purpose cleaners. Store all chemicals, aersols cans in areas that are not accessible in locked cabinets, closets and desk drawers. 30.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 01/27/2014
Score: 85.5

#  Comments Points
3. B. Increase the water pressure to above the mouth guard for the drinking fountain in the cafeteria. 0.0
4. A. The wall in the boy`s restroom 2314 is worn,repair. Worn wall in restroom 3207 in the corner. B. Repair the broken urinals in the boy`s restroom 7104. Repair the toilet in the girl`s restroom 7102. Replace the worn toilet seat in boy`s restroom 1234. C. Broken floor tile in the boy`s restroom 1216, missing coving tile in the girl`s restroom, 5102, repair. 35.0
5. A. Provide a paper towel dispenser at the hand sink in the sick room 1202C. 20.0
6. The gym ceiling cover is torn in several places,repair. Repeat. Floor tile is worn/broken in room 1229, 1225,1214 in the hallway by classroom 1225, in the hallway by room 1209, hallway by restroom 3207, hallway by room 3112. Chipping paint on the stairs that lead to the gym and in stairway S4, repair. Cement stairs are cracked that lead to the 6th grade hallway,repair. Floor in classroom 6206 has a gap by the window sills that is dirty, recommend filling this in with concrete that is sealed. Cracked cement floor in the auditorium, repair. Holes in the walls in class room 1209 and room 219 Floor is dirty on the sealed concrete in the auditorium and under and behind the bleachers in the gym, clean more frequently. Water damaged ceiling tiles in the art room, repair. 30.0
7. B. Keep all storage off the floor on shelving or in cabinents for the following storage closets: the kiln room, equipment room in the gym, 1241 and 1201H. 10.0
8. Classroom 2302 window sills and HAVC by window sill is dusty. Window sills are dusty in the stairway landing area by room 6112. Clean these areas more frequently. 20.0
11. Chlorox wipes and hand sanitizer are stored in several of the classrooms accessible to children. Store out of reach of children or in closet or cabinets when not in use. Chemicals were found in classrooms stored accessible to children this includes: Febreeze, lysol cleaner, goo gone, white out, kilz paint. Store all chemicals, aersols cans in areas that are not accessible in locked cabinets, closets and desk drawers. 30.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 02/15/2012
Score: 84

#  Comments Points
3. Repair damaged water fountains in media center and on 1200 hall. 20.0
4. Repair/Repaint bathroom ceilings that have peeling paint. Ex: Bathroom 1216 ceiling and boys locker room bathroom. Repair clogged or nonfunctional commodes/toilets in 8th grade hall boys bathroom, 7th grade hall boys bathroom, lower 7th grade hall boys bathroom, and in gym boys bathroom. 35.0
5. Repair clogged sinks and sink traps in classrooms # 1208, 2208, and 12237. 15.0
6. Repair gym ceiling cover. Repair damaged floor cover on 8th grade hall. Seal crack at base building seam/floor at room 6203. Media center carpets need cleaning. Repair areas of loose floor tile in upper 7th hallway. Repaint areas of peeling wall paint on 6200 hall. Reattach/repair loose metal columns in gym hall. Repair areas where walls are damaged. Ex: Hole in hall wall at door to room 6201 and wall crack in upper 7th grade hall. Replace damaged or missing wall/base tile in student bathrooms and in areas like lower 7th grade hall stairwell. Replace damaged ceiling tile in 6100 hall. 15.0
7. Storage areas must be kept clean. Ex: 8th grade science lab stockroom had cookie/food crumbs on the floor. 10.0
8. Dust buildup and residue was present on ceiling vents in 1200 hall classrooms, 4200 hall/media center, and in upper 7th grade hall classrooms. Vent covers should be cleaned regularly. Air conditioning system vent filters may require more frequent replacement by Wake County School System maintenance staff. 20.0
9. Repair peeling ceiling cover in gym locker rooms. Ex: Boys locker room. 15.0
11. Cleaning chemicals like chlorox wipes, lysol wipes, aerosol spray cans, industrial stength cleaning chemicals in spray bottles, and white board cleaner were left out in accessible class room areas to students throuhout the building. Chemical products that are toxic, flammable, caustic, are in pressurized containers or have noxious fumes must be stored in areas not accessible to students. Ex: Closed or locked cabinets, stockrooms, closets, or desk drawers. Killz paint should not be stored in sickroom bathroom 30.0
General Comments
Office supplies should not be stored in sick room bathroom.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 09/28/2009
Score: 94

#  Comments Points
4. the ceiling paint is flaking off in the girls bathrooms 1212; smaller bathrooms like 1204 B, 3104 A, or 3104 B also need washable ceilings ( no acoustic ceiling tile ); repair one commode in 1234; many of the commodes have several layers of cauling at the base; some of the caulking is shrinking and discolored; many commodes have a yellow ring or yellow streaks inside the bowls 15.0
6. repair the gym ceiling; peeling paint on the hallway walls in 7000 hall and in the boys locker room; replace two ceiling tiles in art room 6101; repair dry wall outside rooms 3112 and 3105; the media center carpet is stained; repair the carpet in room 3210; the hallway corners need more attention during floor cleaning ( build-up in gthe corners ); repair hole in the wall outside room 6201; the carpet on 3200 and 3100 hall has a lot of stains; 6205 carpet is stained; the carpet in the auditorium apprears worn 15.0
8. several rooms at the beginning of the 1200 hall have older heating units under the windows; paper and other debris is on the inside of the heating units ( the same is happening in the older heating units in the hallways ); clean the windows and window sills, especially in 6112 staircase; dust the ceiling tiles around ceiling vent covers where needed; dust the light fixture above stage and auditorium 20.0
11. found mouse droppings in the cabinets in 1203, 1208, and 2300 hall 10.0
General Comments
GC # 5 : the hand sink faucets in 5102 and 5101 are corroding; the sinks in 1212 are rusty ;
GC # 7 : the storage areas need dunnage racks to keep heavy items off the ground; 1200 hall lockers show signs of aging like worn paint; one set of lockers in the boys locker room is damaged ;
GC # 3 : regulate one fountain outside the cafeteria and repair the fountain outside room 1232
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 08/05/2008
Score: 95

#  Comments Points
4. the ceiling paint is flaking off in the boys and girls bathrooms at the beginning of the 1200 hall ( older part of the building ); replace broken base tiles in 1234; smaller bathrooms like 1204 B, 3104 A, or 3104 B also need washable ceilings ( no acoustic ceiling tile ) 15.0
6. repair the gym ceiling; attach base cove outside room 3205; some older parts of the building have peeling paint on the hallway walls ( like the hallway leading to the locker rooms ); the insulation material on a pipe in 1207 is breaking off 15.0
8. windows and blinds still need to be dusted in some rooms; replace cracked window panel at the entrance to the auditorium; provide a shielded light fixture for the bathroom in 1204 B; several rooms at the beginning of the 1200 hall have older heating units under the windows; paper and other debris is on the inside of the heating units; clean the windows in 6112 staircase 20.0
General Comments
GC # 7 : remove storage out of bathrooms 3104 A and B and 1204 B ;
GC # 3 : one fountain outside the cafeteria needs to be adjusted ;
Note : please remind teachers to keep all cleaning chemicals locked away when the children are in the classroom
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 08/28/2006
Score: 94.5

#  Comments Points
6. paint peeling off the walls in 2300 hallway; replace stained ceiling tiles; repair ceiling in hallway outside 6110; repair gym ceiling 15.0
8. clean vents in locker rooms; noise coming from a vent in boys locker; paint flaking off insulation on pipes in 1205 20.0
9. clean or replace shower curtains in locker rooms 20.0
General Comments
Notes : remove debris out of old heating element outside 1209; repair fountain near 1230; two broken baseboard tiles in 1234; trailer 3 has a lot of damage to siding on the outside
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 09/01/2004
Score: 93

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 06/03/2003
Score: 95

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Ligon Middle School
Location: 706 E LENOIR ST RALEIGH, NC 27601-2029
Facility Type: Schools
Inspection Date: 09/07/2001
Score: 97.5

#  Comments Points
General Comments