Repair water fountain with leak beneath it at the entry to the boy`s bathroom #112A. Repair two nonfunctional water fountains adjacent to the entrance of the girl`s bathroom #404B.
20.0
4.
Repair clogged and nonfunctional urinal in boy`s bathroom #404A. Repair clogged and backed up toilet in staff bathroom #608T. Repair toilet that has poor water flow for flushing in the girl`s bathroom #503.
20.0
5.
Repair leaks behind and beneath both hand wash sinks in classroom #507.
15.0
6.
Repair the sources of ceiling leaks in the following school building locations: in girls bathroom #112B, in the front lobby at the entrance to room #104, at the entrance to the 500 hallway, in the 400 hallway across from computer lab #401, in the 200 hallway over the ramp, at the entry to the 400 hallway, in the 400 hallway at custodial closet #415, in classroom #510, in the media center stock room #204, and over the gym stage. The ceiling leak at the entrance to the 500 hallway has possible mold stains on the ceiling panels. The leak at the entrance to custodial closet #415 was actively dripping at the time of inspection. Water stained ceiling panels caused by the ceiling leaks in the location listed should be replaced after the leaks have been fixed. Repair and reattach loose riser boards on the steps from the gym floor to the stage. Priority repairs for safety are needed to prevent trip and fall hazards. Reattach loose wallpaper in classrooms #511 and #507. A cover plate is needed to seal over the hole in the lower wall of the special needs kitchen class bathroom #615B.
15.0
8.
Replace missing ceiling vent cover in the gym.
20.0
11.
Build up, grime, and residue is covering the surfaces of the playground equipment structures adjacent to the basketball court and the athletic field and is also on the pre-k playground equipment structure. Pressure washing is needed to clean this playground equipment. Replace splintered hand railings on the wooden ramp and steps on the outside amphitheater stage. Replace rotted and loose floorboards also present on the outside theater stage to prevent trip and fall hazards. Priority repairs for safety are necessary on both the stage handrails and the floorboards.
Repair two nonfunctional drinking fountains in the hallway adjacent to the boy`s bathroom #404A. Repair drinking fountain in hallway adjacent to custodial closet #415. This drinking fountain is missing a press hand paddle side cover.
20.0
4.
Repair toilet in the end stall of boy`s bathroom #112A. This toilet is leaking on the plumbing pipework. Repair toilet that has a broken seat in the first stall of the girl`s bathroom #404B. Repair toilet in staff bathroom #518T. This toilet is leaking on the plumbing pipework and has poor water flow for flushing. Repair toilet in classroom bathroom #507A. This toilet is leaking on the plumbing pipework. Repair toilet in the third stall of the girl`s hall bathroom #503. This toilet has poor water flow for flushing and requires a new flush valve .
20.0
5.
Replace broken paper towel dispensers in classroom bathrooms #512A and #517A. Repair leak on base of countertop handwash sink faucet in classroom #515. Repair handwash sink that is leaking at the drainpipes in classroom #507.
35.0
6.
Repair the sources of roof and ceiling leaks in the following school locations: in the 100 hallway by staff bathroom #109B, in the hallway by room #107, in the hallway by room #104, inside of room #104, and in the art class stock room #411A. Replace water-stained ceiling tiles in these locations after the sources of these leaks have been repaired. Reattach or replace loose wallpaper in classrooms #506 and #507. Repair and reattach loose sliding wall panels between the cafeteria dining room and the gym multi-purpose room. These wall panels have gotten off track and require priority repairs for safety to prevent pinch hazards from the now open spaces in between the disconnected panels.
15.0
11.
Four live cockroaches were observed in the dishwasher of the special needs class kitchen #615 at the time of inspection. Professional pest control treatments are needed throughout the special needs class kitchen. Keep food items in the kitchen sealed in plastic containers and clean surfaces and equipment regularly of food crumbs and residue.
10.0
General Comments
Reattach loose ceiling light shield covers in classrooms #502 and #510. Repair flickering ceiling light in girl's bathroom #503. Remove or replace small play tunnel on the pre-k playground. The exterior cover of this tunnel is cracked and has sharped broken edges. Priority repair, replacement, or removal is necessary to prevent injury hazards. Overgrown brush area adjacent to the front entrance sidewalk of the school building requires trimming to prevent pest issues.
Repair two nonfunctional drinking fountains in the hall way at the entrance to boys bathroom #404A.
20.0
4.
Reattach loose piece of metal stripping on the base of toilet stall divider wall in boys bathroom #112A.
20.0
5.
Repair loose faucet on hand wash sink in classroom #507.
15.0
6.
Repair ceiling leaks in the hallways at the entrances to staff bathrooms #109B and #407B. Replace water stained ceiling tiles after the sources of the leaks have been fixed.
Repair nonfunctional water fountain in hallway by girls bathroom #404B. Repair water fountains in classrooms #513, #517 and in #518. These water fountains have low water pressure.
20.0
4.
Repair leaking toilet in the girls hall bathroom #112 B.
20.0
5.
Repair hand wash sinks in special needs classroom bathroom #615B and in classroom #507. Both of these hand washing sinks have low water pressure.
15.0
6.
Repair ceiling leaks in classroom bathroom #507A, in the boys hall bathroom #112A, and in the hallway outside of room #107. Replace water damaged ceiling tiles and repair water stained ceiling in the bathroom after these leaks are repaired.
15.0
8.
Repair nonfunctional ceiling light fixtures in the media center.
20.0
General Comments
Children's sleep cots were stored in classroom bathroom #511A. Children's tricycles were stored in class bathroom #507A. Bathrooms are not clean storage locations. The storage of these items in bathrooms is also an impediment to the cleaning and repair of these facilities. These items should be removed from these locations A.S.A.P.
Water fountains in classrooms # 515, 615, 612, 510, 513, 518, and 110 have low water pressure or are nonfunctional. Water fountain in classroom # 610 has a clogged drain. Repair water fountains.
20.0
4.
Repair damaged floor tile in classroom bathroom # 512 A.
15.0
6.
Wall paint in music room is peeling. Wall paper in classroom # 507 is loose. Repair ceiling leaks in classroom # 502, art room # 411 kiln room, and hall ceiling leak at custodial closet # 109 A. Replace water damaged ceiling tile after leaks are repaired.
15.0
8.
Air conditioning system in classrooms # 512 through # 518 does not appear to be functioning. Rooms are very warm compared to the rest of the building. Please repair.
20.0
11.
Courtyards by ladybug statue and at kindergarten playground are overgrown and require mowing and clearing to prevent pest and mosquito issues. The grounds by the school garden and the track are also overgrown and require mowing. Wasps are present in classroom # 608. Contact the school systems maintenance section to have pest control treatments for this room and it`s air conditioning vents completed before students return.
25.0
General Comments
Hammer loose nails back into wooden wall of amphitheater. Reattach loose floor board on wooden step in front of amphitheater stage. Class supplies and cots were stored in class bathroom # 511. Class supplies were also stored in the health room bathroom. Bathrooms are not clean storage areas. Items like class supplies, toys, equipment, and cots stored in restrooms are an impediment to cleaning. Please remove all these items from restrooms A.S.A.P. Keep divider wall open in room # 601- A to prevent excess humidity from air conditioning systems in an otherwise small and confined space.
There was a hole in the floor cover in front of room 103. The walls around 404 A&B the boys and girls restroom need to be repainted. In room 513 A the walls need to be repainted.
A) The water fountain in room 609 is not working, repair.
20.0
5.
A) The handsink in room 609 has very low pressure, repair.
15.0
General Comments
There is storage in the bathroom in room #507; according to the teacher in that classroom, the bathroom is not used. If the bathroom returns to use, the storage must be moved out of the bathroom.
Repair damaged carpet in 518 and 120, and damaged transition strip in 608.
15.0
8.
The HVAC unit in M 514 is very noisy and has a leak at one of the valves, the unit in M 504 squeeks loudly, and a belt in M 408 is running louder than usual.
Clean the stage curtains ( dust build-up ).
20.0
General Comments
GC # 4 : The paint on the walls behind the commode in boys bathroom 505 is flaking. GC # 5 : One of the sensors at the hand sink in boys bathroom 404 A is not working.
Adjust the water pressure at the fountains in 512,515,518. The fountain in 517 has a very small leak.
20.0
6.
Room 114 has a leak in the ceiling ( ceiling tiles were removed, and a bucket and some plastic wrap were placed under the leak ). Repair the leak. Replace stained ceiling tiles in room 510.
Several cracks in the walls were repaired with putty. The children have started to peel out pieces of the putty.
15.0
8.
One of the top windows in the gym has a hole. Replace the window.
20.0
General Comments
GC # 11 : Please remind teachers that all chemicals including cleaners and Chlorox wipes need to be in a cabinet at least 5 feet above the floor ( out of reach of children ). Also remind them to remove any bait dishes from the window sills. The dishes smell enticing and should not be left where children can reach them ( and if there are no ants in the room, ant bait will draw them to the room ).
one of the fountains next to room 415 needs repair, and the water pressure on the other one needs to be adjusted
20.0
4.
paint the walls behind the commodes in boys bathroom 505; the hand sink in boys bathroom 404 A does not work
20.0
6.
replace stained carpet tiles ( computer room and room 604, for example )
15.0
General Comments
GC # 7 : additional shelving may be needed to keep all supplies in book storage rooms and custodian closets off the floor ; GC # 13 : please remind teachers that chemicals like Chlorox wipes, sanitizers, disinfectant sprays, and cleaners need to be kept out of reach of the children ( in a locked cabinet or on a shelf more than 5 feet off the ground )
adjust the fountains in Ladybug Lodge; the water pressure is too low
20.0
4.
the ceilings in all bathrooms need to be washable ( no acoustic tile ); very strong odor in boys room on 4th/5th grade hall
15.0
6.
blue paint is flaking off the windows on the inside and outside of the building; the carpet in the media center is stained; replace a stained ceiling tile near the window in the media center; wax is building up in the corners; in the modular buildings, repair damaged halway wall corners
15.0
8.
clean the bathroom vents in the permanent building and the modulars; clean the duct work in the auditorium
20.0
11.
please remind teachers to keep all chemicals including disinfectant wipes, Expo, and other cleaners out of reach of the students or in a locked cabinet
30.0
General Comments
Note : the building is still undergoing construction ; many of the violations cited above will be corrected during the remodel ; Gc # 7 : provide dunnage racks for heavier items in the storage rooms ( replace the pallets )
repair fountains in 213 and across from 204; adjust fountain in 210
20.0
4.
the ceilings in all bathrooms need to be washable ( no acoustic tile )
15.0
6.
repair moldy wall section in R 4; check wall behind cabinets in R 2 for water damage and mold; ( and repair the leak that causes moisture damage ); the carpet shows significant signs of aging ( torn areas; wax seeping into the carpet; carpets seams are breaking open ); repair broken floor tiles near 115; replace stained ceiling tiles in the trailers; one ceiling tile in the drama trailer may have mold
15.0
8.
mold forming in the insulation material on the outsdide of duct work in 2nd/3rd grade hall; also some mold forming on duct work near 107; dust off the vent grids in the bathrooms; provide light shields for the light fixtures in the student bathrooms; one vent in a girls bathroom in the 100 hall needs repair ( needs to be pulled up and attached to the ceiling )
20.0
General Comments
NOTE : REMIND TEACHERS TO KEEP ALL CHEMICALS OUT OF REACH OF CHILDREN ( 5 FEET OFF THE GROUND OR IN A LOCKED CABINET ); GC # 7 : remove storage out of Kindergarten bathrooms; replace rusty storage racks and keep all storage off the floor ; GC # 11 : the outside of the storage shed behind the school needs repair