This domain has not been activated. Tyler Technologies Environmental Health
Health Inspections Home :: FAQ  
 




Facility



Broughton High School


723 SAINT MARYS ST
RALEIGH, NC 27605-1424

Facility Type: Schools
 

Related Reports

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 06/20/2024
Score: 86.5

#  Comments Points
3. Repair loose spray nozzle on center drinking fountain in the hallway of trailer one. 20.0
4. Repair major ceiling leaks present in the gym girls bathroom #1611B. The ceiling is extremely water damaged in this bathroom and has collapsed in some sections. Priority repairs are needed to stop the causes of theses ceiling leaks and to repair the water damaged bathroom ceiling. Repair damaged wall covering in the trailer #2 boy`s bathroom. Floor drains in the auxiliary gym boys and girls bathrooms #0204 and #0205 are backing up frequently with waste water. These clogged floor drains require priority repair or replacement to prevent future sewage backups. Repair and replace loose and broken floor tiles around the floor drain in the toilet stall in the boy`s locker room bathroom #1616. Replace missing wall light switch cover in the trailer one boy`s bathroom. Priority repairs are needed to prevent electrical hazards. Repair one clogged toilet and two clogged urinals in boy`s bathroom #1403. Repair one clogged toilet in girl`s bathroom #1405. Repair one clogged urinal in the boy`s bathroom #1206. Repair one toilet that has a broken flush valve handle and another toilet that is nonfunctional the trailer one boy`s bathroom. Repair one toilet and one urinal that are both nonfunctional in the boy`s bathroom #2403. Repair one urinal that is leaking on the plumbing pipework in the trailer #2 boy`s bathroom. Repair two nonfunctional toilets in the trailer #2 girl`s bathroom. Repair three clogged urinals in boy`s bathroom #154. Reattach and repair one urinal that has become partially detached from the wall in boy`s bathroom #154. Repair toilet that has poor water flow for flushing in the cafeteria boy`s bathroom #419A. Repair nonfunctional toilet in the girl`s bathroom #2405. Repair one nonfunctional toilet and one toilet that has both a broken seat and poor water flow for flushing in the cafeteria girl`s bathroom. Repair one nonfunctional toilet and one toilet that has a broken seat and is leaking on the plumbing pipework in girl's bathroom #1261. Repair one urinal that has poor water flow for flushing in boy`s bathroom #254. Repair ceiling leak present in staff bathroom #3407. Replace water damaged ceiling tile in this bathroom after the source of the leak is fixed. Replace two missing bathroom toilet stall doors in boy`s bathrooms #154 and #254. 50.0
5. Replace broken off, severely damaged, and nonfunctional bathroom hand wash sinks and faucets in the trailer #2 boy`s bathroom, in boy`s bathroom #2208, in boy`s locker room #2630, and in girl`s bathroom #2405. Repair loose faucet on hand wash sink in boy`s bathroom #154. Replace broken and loosely attached paper towel dispensers in boy`s bathrooms #1206, in boy`s bathroom #3403 and in the cafeteria girl`s bathroom. 35.0
6. Repair chipping and deteriorated plaster wall surfaces beneath windows in classrooms #3214A, #3214B, and #3218. There is major water damage on these wall surfaces. The wall damage may be the result of leaks around the windows in these classrooms. The sources of these leaks and water damage should be identified and repaired. Repair the sources of ceiling leaks present in the hallways adjacent to the girl`s bathroom #2316 and at staff restroom #1401. Repair ceiling leak present in the ROTC classroom #0211. Repair ceiling leak in the cafeteria dining room adjacent to the central skylight. Replace water stained ceiling tiles after all of these leaks have been fixed. Replace chipped and broken floor tiles in the hallway at the entrance to boy`s bathroom #1403. Repair floor drain that is backing up and overflowing frequently with waste water in the ROTC class office #0211. This floor drain pipe should be repaired or replaced to prevent sewage from backing up into the building. Repaint peeling paint on ceiling rafters in the main gym and on the ceiling of the auxiliary gym. During heavy rainfall the the hallway at the exit doorway by room #305 floods. Drainage diversions including gutter downspout extensions are needed to redirect rainfall runoff away from the building foundation and entry ramp at this exit. Priority repairs are needed to prevent flood water damage to interior floors and walls and to prevent possible interior mold growth. 15.0
11. Remove vines including Virginia Creeper and possibly Poison Ivy that are growing on the exterior building walls in the central courtyard. 15.0
General Comments
Repair leaking shower head nozzle in boy's locker room #2630. School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 11/02/2020
Score: 91

#  Comments Points
3. Repair drinking fountain by room 2626. Fountain has low pressure. 20.0
4. Repair nonfunctional toilet in the girls hall bathroom #160. Repair nonfunctional urinal in the modular building #2 boys bathroom. The urinal has poor water flow. Replace damaged toilet stall wall panel in boys bathroom #254. (Rear stall). 20.0
5. Repair damaged coating in hand wash sink basin in boys bathroom #254. 15.0
6. Repaint peeling paint on ceiling rafters in the main gym and on the ceiling of the auxiliary gym room #1201J. Repair ceiling paint that is peeling on the exterior entry porch by the auxiliary gym. Repair chipping wall paint in girls bathroom #1407, boys bathroom #1206, and in staff bathroom #3407. Repair peeling ceiling paint in boys bathroom #1401, girls bathroom #2405, girls locker room #2632. and in boys bathroom #3403. Repair peeling wall paint in stairway #6, in the hall by custodial closet #2212, in the computer lab #3404, in the 3400 hallway by the courtyard windows at rooms #3404 and #3401, in the 2200 hall by room #2207, and in the 2400 hall by room #2404. Repair ceiling leaks in staff bathroom #3407, in the 1400 hall at the courtyard entrance and room #1404, in girls bathroom #1324, in the mothers room #152, in classroom #162, in the main gym boys locker room # 1615A, on the second floor of the main gym by girls locker room #2632, main gym girls bathroom #2634, main gym conference room #2604, in the cafeteria dining room by the skylight and kitchen entrance, in the cafeteria by room #419M and in the main gym lobby entrance by room #1622. Repair damaged hall floor tile by room #3306. Repair loose floor tile by room #0305. Repair chipped floor tile in toilet stall in the main gym boys locker room bathroom #1615A 15.0
8. Repair nonfunctional ceiling lighting in the entry room #1308 to the auditorium. Dust build up is blowing out of ceiling vents in classroom #2608. Filter replacement is needed for this section of H.V.A.C. 20.0
General Comments
Repair damaged top of corner locker in the main gym girls locker room #1611. Sharp metal edge is exposed on this damaged locker top. (Safety Concern) Repair of elevator with the ground floor landing on the 1300 hall is needed to allow ease of access and departure for students and staff with disabilities. Please repair elevator.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 07/18/2018
Score: 86.5

#  Comments Points
3. Repair nonfunctional water fountains in pod class room buildings. Repair water fountain paddle that is taped in gym ground floor hall. 20.0
4. Repair nonfunctional commodes and urinals in pod class building bathrooms. Repair nonfunctional commodes and urinals in restrooms in cafeteria. Repair nonfunctional commode in girls bathroom on 1400 hall. Repair nonfunctional commodes in third floor girls restroom of original building. Bathroom fixtures (Commodes) in pod building have mold growth and residue inside and require cleaning. Walls and ceilings in original building bathrooms have chipping and peeling paint and require repainting. Window sills in original building bathrooms have chipping paint and also require repainting. Repair damaged stall door in boys bathroom on 1400 hall and damaged stall interior in boys room on third floor hall. 35.0
5. Repair nonfunctional hand wash sink in student bathrooms in cafeteria. 15.0
6. The carpet in room 3214 is very stained and smells musty. Recommend replacement. Repair ceiling air conditioning leak in class room 1217. Replace water damaged ceiling tile after leak is repaired in this room. Walls in hallways and classrooms throughout original building are chipped and require repair and repainting. Replace damaged floor tile in science building ground floor hallway at bathrooms. Replace loose floor tile in room number 1218. 15.0
8. Dust build up was present on ceiling vents in science building lab classrooms. Cleaning of vents and air conditioning systems filter replacement is required. Dust build up was also present in ceiling vents in auto shop class rooms. 20.0
9. Repair nonfunctional showers in gym building locker rooms. Clean up residue and debris in crevices between benches and lockers in boys gym class locker room. 30.0
General Comments
Repair damaged lockers in boys locker room in gym. Remove torn cloth chair from football team locker room. This chair can not be kept clean and should be discarded. Repair/seal or replace weight room equipment that has torn upholstered covering.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 07/26/2016
Score: 93.5

#  Comments Points
4. There is a crack in the wall close to the window in the womens bathroom on the third floor. The paint in bathroom 2316 is flaking. Paint in the mens room next to room 2210 is flaking, and there are a lot of dead insects on the ceiling near the windows. The ceiling in one of the mens locker rooms is starting to flake. 15.0
6. The carpet on the third floor is showing definite signs of wear. Replace damaged floor tiles in 3103. Paint the walls in the 3100 hallway ( stains ). A possible roof leak has caused water damage to the walls in one corner in 3304. Paint is peeling in 2311, 2406, 2212, 1320, 0301. There is a possible leak in 2215. The carpet in the media center is very stained. The walls throughout the first floor need to be patched and painted. Repair flaking paint and missing base boards in 1218. The floor tiles in 1200 hall are moisture damaged ( corners curving up ). The paint on the metal structures of the gym ceiling is flaking off in large patches. 30.0
8. Dust the light fixture and other hanging fixtures in the dance room. The paint on the window sill in 1326 is flaking badly. 20.0
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 06/12/2015
Score: 90.5

#  Comments Points
3. Water fountain by 2624 must have the water pressure increase to produce an arch. 0.0
4. A)Chipping paint/wall repair: ceiling in boy's locker room; ceiling in girl's locker room; hole in wall in girl's restroom in Pod #1; holes in walls in boy's restroom in Pod #2; Rm 1324 chipping paint in girl's restroom; Rm 2316 paint peeling on wall/ceiling; B)1612-enamel on one sink is worn off and needs repair; two toilets in girl's locker room do not flush; Rm 2636-enamel on sink worn away and needs repair; Rm 2636 faucet handle broken off; 3213A toilet not flushing; Rm 3401 toilet does not flush; Rm 2316 two toilet do not flush; Rm 1401 two toilets do not flush; Rm 1407 low flow on faucet; Rm 1407 4th stall toilet does not flush; 0313 toilet not flushing. 20.0
5. B) No paper towels in boy's restroom Pod #1; No paper towels or holder in girl's restroom in Pod #2; 1201E paper towel holder hanging on by one nail; Rm 0313 no towels or soap in boy's restroom. 20.0
6. Throughout the school, the walls in the hallways need cleaning and repair, there are many areas of chipped plaster. Rm 1626-replace ceiling tile; Paint peeling off from ceiling in gym; Rm 104-wall paint bubbling off in girl's restroom (Auto Shop); Rm 3218 stains on carpet; Rm3219A paint chipping from ceiling; Rm 3219 paint bubbling on walls, coving coming away from walls; Rm 3212 walls peeling, missing tiles; Rm 3314 stain on carpet, corner wall & ceiling paint chipping; 2313 peeling paint on walls by back window, peeling paint on ceiling by front window; Rm 2307 repair wall by window; Rm 2310 chipping paint on wall; Rm 2100B repair coving; Rm 2302A paint bubbling off wall on left; Media Center paint chipping over Biography section; 2200 hallway chipped plaster and paint on walls; Repair floor by Rm 2207; Rm 2208 broken tile, paint chipping on walls; Rm 2215A & D chipping paint; Rm 1402 replace cracked tiles; 1200 hallway paint chipping on walls; Rm 1208 repair wall; Rm 1215 peeling paint; paint chipping on walls in Little Gym; mold growing on ceiling in Little Gym; floor cracks in Little Gym; Rm 0217 chipping paint on wall; Rm 0209 chipping paint on wall in Wrestling Room; Rm 0207 paint chipping on wall, floor cracked; Rm 0317A paint chipping on wall. 30.0
7. Storage on the floor: Rm 3219, Rm 1318, Rm 3213B, Rm 229; Rm 1203; 0211A; 10.0
8. Clean air vent in 3401 0.0
9. B)Rm 1626-couple of pads in weight training room torn and need replacing; Rm 2620-mat in sport injury room is torn and needs replacing; 0.0
10. B)Mop sink in gym leaking. 0.0
11. Car oil not properly stored; have oil cleaned up. 15.0
General Comments
Rm 2620-drain cover is a possible trip hazard and suggest putting a cover to prevent an injury with the open hole but still allows water to drain. Be sure teachers store any chemicals in lockable cabinets.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 06/11/2013
Score: 93.5

#  Comments Points
4. The walls and ceilings in several restrooms throughout the school have peeling paint on the walls and ceilings, especially around windows and HVAC units; repair walls and ceilings where needed. Clean the walls below the soap and papertowel dispensers in the 1st floor restrooms. 15.0
6. Throughout the school, the walls in the hallways need cleaning and repair, there are many areas of chipped plaster. There is severe moisture damage and some mold in the hall across from room 1213, also in this area, there appears to be either moisture or termite damage to the baseboards, the wall and baseboards need to be repaired. Many classrooms throughout the older parts of the school have damage to the walls and ceilings, especially on exterior walls and around windows, repair these arear. Observed moisture damaged ceiling tiles and ceilings in the following rooms: 2404, 2407, 1320 and 1326. On the science rooms and science supply areas (151, 152, and 161-164) on the 1st floor, there is moisture damage around light fixtures and HVAC fixtures, repair these areas. Repair the crack and damaged plaster in the 1st floor stairwell near the cafeteria. The floor in the 1st floor custodial closet (1305) needs additional cleaning on the floors after an old sewer leak. The ceiling in 161-164 is sagging, the supports are rusted, repair. Several areas of the basement below the auditorium are damaged, repair walls. There is heavy mold growth in the boiler room floor, this area needs thorough cleaning, there also appears to be some moisture seepage from a behind a corroded metal plate on the wall. The window tinting on the 2nd and 3rd floors of the new wing is peeling, repair tinting. 30.0
8. The HVAC vents and returns throughout the school are dusty, some have mold, clean vents. Recommend thorough cleaning of HVAC duct work throughout the school. The light in the custodial closet (3216) is out, replace light. The HVAC drain in the custodial closet (1305) is draining onto the floor, adjust pipe so that it drains into the sink instead of onto the floor. 20.0
General Comments
#1(C) Several custodial closets have chemical dispensers hooked up to faucets with atmospheric vacuum breakers (AVB) but no pressure rated backflow prevention, AVBs are not designed to have any shut offs downstream and could malfunction and allow backflow. All mops sinks with chemical dispensers must have pressure rated backflow prevention.

#7(B) The supply closet (1318) has storage on the floor and the floor is not clean, storage should be stored in a manner that facilitates cleaning of the floors.

There is evidence of flooding in parts of both basement areas, the doors in these areas need to be properly sealed so that water doesn't come in, currently there are gaps under the doors. The water appears to be coming down the stairs from the outside and the drains in these areas seem to be clogged or non-functional
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 04/01/2011
Score: 93

#  Comments Points
3. B) The water pressure in 2 water fountains was low, adjust the pressure at the following water fountains so that the stream of water is above the mouth guard: fountain next to room 362 and fountain by room 251. 20.0
4. A) The walls behind the toilets and urinals in the boys restroom on the science wing has peeling paint, repair these areas. The wall below the soap dispenser in the girls restroom on the science wing needs to be repainted. In the 2nd and 3rd floor science wing restrooms, the area below the paper towel dispensers need to be repair, there is an open area below that needs to be tiled. There is some moisture damage to the walls in the 1st floor ladies restroom near the stairwell. B) Repair the broken toilet seat in the girls restroom on the 3rd floor near the doorway to the science wing. On the 3rd floor science wing, the toilet seat in the handicapped stall is worn, repair or replace. 35.0
6. There is moisture damage to the plaster walls below the windows on the on the 3200 hall and near the elevator on the 3rd floor, repair. There is moisture damage to the walls in the following classrooms: 3103(far right corner and behind TV), 3207(around the windows), and 3306(corner next to window). Clean the lower parts of the walls in the stairwells. The paint on the window sill in the girls restroom on the 3rd floor near the doorway to the science wing has peeling/chipping paint and the wooden sill underneath is exposed, repair this area. 15.0
8. General Comment: The air vents and exhaust vent covers in most restrooms need cleaning, this includes the handicapped accessible restrooms, they are dusty. The air conditioner vent in room 3207 needs cleaning. 0.0
11. General comment(A): Remove all storage from around the dumpster behind the cafeteria, also need to remove the leaf litter, this is a potential pest or rodent harborage or breeding area. 0.0
General Comments
The special needs students' restroom needs to be supplied with disinfectant that can be sprayed on the toilet, floor around the toilet, and handwashing sink after toileting is finished. Disinfectant should be sprayed on surfaces and allowed to air dry or the minimal amount of time for disinfectant to be effective as stated on the label.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 06/17/2009
Score: 95.5

#  Comments Points
3. B. Provide adequate pressure to the drinking fountains above the mouthguard in pod 2 and and on the 3rd floor of the main building. 20.0
6. 1st floor main building the wall in the hallway is worn by the door by leading to the gym. Walls are worn on the 3rd floor hallway by room 3210 and in the basement hallway. Repair worn walls in the dance room, in the shop,room 0304, 0309,wrestling room, in the graphic room by the handsink,room 3306(water damaged). Replace worn floor tiles in room 0301, room 157, room 3301, music room. Replace/repair water damaged ceiling tiles in room 151, in the graphics room, small gym worn ceiling, in the boy`s locker room on the 2nd floor of the main gym shower is water damaged. 15.0
7. Keep all storage off the floor 8" on shelving in the dark room, closet 158, interior design storage room, main custodial closet, basement storage closet(custodial), and room 1617 storage closet. 10.0
General Comments
Vents are dirty in the boy's and girl's locker rooms on the 2nd floor of the gym. 2 showers are broken in the girl's big gym locker room on the 2nd floor repair. Re-enamel the sink in the girl's restroom in the 2nd floor of the gym. The girl's handicaped restroom in pod 2 the lighting is low.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 06/24/2008
Score: 91

#  Comments Points
4. Repair nonfunctional commodes in third and first floor hall restrooms. 20.0
5. Repair all nonfunctional handwash sink faucets in student bathrooms. Ex: Third floor hall restroom. 15.0
6. Repaint halls and class walls where paint is peeling Ex: Third floor and performance arts hall on second floor. Repair damaged floor tile on second floor performance arts hall. Clean floor in greenhouse on second floor. Verify repair of all ceiling leaks in facility. Replace water damaged ceiling tile after leaks are repaired. Ex: Second floor science lab classes. 15.0
8. Clean ceiling vents of dust buildup. Ex: Men`s locker room, weight room, and science lab classes on second and first floor. 20.0
9. Repair broken shower in mens locker room. 20.0
General Comments
Repair nonfunctional eyewash in automotive workshop. Handwash sinks are needed in student bathrooms for automotive workshop and for weight room. Remove discarded furniture and debris from premises by auto workshop. Remove cloth couches and chairs from mens locker room. These pieces of furniture are not water proof or cleanable for a restroom/showering area. Termites are present in rooms along 1400 wing. Contact a pest control specialist to treat these areas while students are off premises for summer break. Bats have been a problem at facility in the past. Verify that all roof areas have been sealed to prevent bats from entering facility. Volatile, flammable, or caustic chemicals must be stored properly in science lab classes. Ex: Acetone was left out on counter top with other chemicals in first floor science lab class near breezeway. Chemicals should be stored according to guidelines on material safety data sheets. Ex: In fireproof cabinets or in designated stockrooms that only faculity can access. Flying insects are present in men''s locker room. Clean toilets, sinks, showers, and floor drains in this area. Contact a pest control specialist.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 03/22/2005
Score: 87

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 06/05/2003
Score: 92.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 05/09/2002
Score: 84.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Broughton High School
Location: 723 SAINT MARYS ST RALEIGH, NC 27605-1424
Facility Type: Schools
Inspection Date: 03/21/2001
Score: 88.5

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment


Keyword (1):
Keyword (2):
Keyword (3):
Score Range:
-
Establishment Type:
Zipcode:
Violations:
Date Range:
- - Start
- - End

Health Inspections Home :: FAQ