Green Hope High School


2500 Carpenter Upchurch RD
CARY, NC 27519

Facility Type: Schools
 

Related Reports

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 06/24/2024
Score: 87

#  Comments Points
3. Repair drinking fountain on the 200 hallway that has a clogged drain. The drain on this fountain is backing up and overflowing. Reattach loose drinking fountain spray nozzles on fountains in modular class buildings #2 and #4. 20.0
4. Repair nonfunctional and damaged toilets and urinals in the following school restrooms: modular #1 girls bathroom, (one nonfunctional toilet), modular #2 girl`s bathroom, (two nonfunctional toilets), modular #4 boy`s bathroom, (one nonfunctional toilet), modular #4 girl`s bathroom, (four nonfunctional toilets), boy`s locker room bathroom #416, (two nonfunctional toilets), boy`s bathroom #3207, (one nonfunctional toilet and one nonfunctional urinal), boy`s bathroom #2207, (one nonfunctional urinal), boy`s bathroom #207, (one nonfunctional toilet), girl`s locker room bathroom #424A, (one nonfunctional and poorly draining toilet.) boy`s #600 bathroom, (one nonfunctional toilet and one nonfunctional urinal), boy`s bathroom #2307, (one nonfunctional toilet), girl`s locker room bathroom #420A, (two nonfunctional toilets), girl`s bathroom #2311, (three nonfunctional toilets), girls bathroom #503, (one nonfunctional toilet in the handicap stall and one toilet that is leaking on the plumbing pipework in the 7th stall), main office women`s bathroom #100M, (one toilet that is leaking on the flush valve), and in modular #3 boys bathroom, (one toilet with a broken and loose seat). Repair and seal large hole in wall of the end bathroom stall in the modular #4 boys bathroom. Repair and seal large hole in the ceiling of the girl`s bathroom #2211 over the rear bathroom stall. Verify that the plumbing leak that caused this ceiling area to collapse has been properly repaired. Repair ceiling leaks in girl`s bathroom #211. Clean this bathroom ceiling of possible mold growth and repaint the water stained ceiling areas with mold resistant paint. Repair ceiling leak in the coaching staff bathroom #403 and replace water stained ceiling tiles in this bathroom caused by the leak. Repair sources of ceiling leaks in girl`s bathroom #2311 and repair chipping and peeling ceiling coverings in this bathroom caused by the leaks. Replace missing plumbing access wall panel cover in boy`s locker room bathroom #416. Repair water damaged and chipping and peeling ceiling covering above shower stalls in the boy`s locker room bathroom #416. Repair broken toilet stall door in boy`s locker room bathroom #416. Replace damaged, loose, and missing wall base tiles in the following school bathrooms: girl`s bathroom #604, (broken wall base tiles in the end toilet stall), office bathroom #108C, (loose wall base tile), and in modular #2 girls bathroom and modular #2 boys bathroom, (missing wall base tile behind toilets). Replace broken and missing floor tiles in the following school bathrooms: modular #3 boy`s bathroom, and in the modular #2 boy`s bathroom at a toilet. Toilets in the boy`s and girls bathrooms in the bathroom trailer had been vandalized and contained human waste. These bathrooms had been closed to use but were left unlocked. If these restrooms are not to be used by students the bathroom doors should be kept locked at all times to keep the public out. These fixtures should be cleaned of the dried bathroom waste and the vandalized toilet with a broken tank casing should be removed from the bathroom. Water flow has already been disconnected in these bathrooms. Replace missing thermostat wall control console covers in the modular #1 boy`s bathroom. Exposed wiring at these missing wall consoles could create an electrical hazard. 50.0
5. Repair hand wash sink faucets that have loose and disconnected water supply lines at the lower water flow control valves beneath the sinks in the boy`s bathrooms in the modular #2 trailer and modular #4 trailer. The boy`s bathroom sink in the modular #2 trailer has no water flow at all and is nonfunctional. Repair loose hand wash sink faucets in the modular #3 girl`s bathroom and in staff bathroom #201. Repair leaking faucet on hand wash sink in girl`s bathroom #503. Repair three hand wash sink faucets that have poor water flow for washing in girl`s bathroom #604. Repair nonfunctional hand wash sink faucet in boy`s bathroom #600. 15.0
6. Replace broken floor boards on the entrance ramp into the modular #4 class trailer. Repair loose handrails on the modular #4 deck entry steps and on the ramp entrance. Replace loose floor boards also on the entrance ramp for modular #4. Priority repairs for safety are necessary on the modular #4 ramp and steps due to the potential of injury hazards from the deteriorated conditions of ramps and steps. Replace rotted floor boards on the entry ramp of modular #2. Repair loose top step board on the entry steps to the deck entrance of the modular #2 class building. Priority safety repairs are needed on the modular #2 ramp and steps to prevent potential trip and fall hazards. The ramps, decks, deck steps, and hand rails are in very poor condition on all of the small class trailers especially trailers #3, #4, #5, #6, #7, #12 and the bathroom trailer. There are loose, warped, and rotted floor boards on the ramps, decks, and steps of these trailers. These trailers also have deteriorated, loose, and warped hand railings. Exposed rusted nail points are present on both the deck and ramp floor boards and on the railings. Major repairs for safety are required to prevent possible injuries from trip and fall hazards, puncture wounds from exposed nail points, and from the possibility of the collapse of deteriorated floorboards, steps, and railings when under use. Repair and replace warped floorboards at the side exterior exit door of the auxiliary gym. Repairs are needed to prevent trip and fall hazards. Replace broken door window in rear entry door of the auxiliary gym. Repair roof and ceiling leaks in the media center, in room #2104, in room #2102, in the hallway outside of room #2104, at the rear entrance to the auditorium #101, throughout the band hallway, in the 2200 stairway, in the dance studio #502, in the athletic wing hall of the auditorium, and in the weight room #406. Repair water damaged ceiling surfaces and replace water stained and water damaged ceiling tiles in all of the identified leak locations after the sources of the leaks have been fixed. Replace damaged and missing ceiling tiles in the weight room and in the hallway at the entry to locker room #420. Replace broken window sash in the weight room. Repair bent and damaged ceiling grid in the weight room. Replace missing lids on the recessed floor plugs in the media center to prevent possible injuries from trip and fall hazards. Carpeting in the media center is permanently stained and in need of replacement. Carpets in classrooms #2104 and #2102 have a strong musty odor from ceiling leak water exposure and are in need of replacement. Repair broken door hinge and broken closing arm on the main entry doors to the auditorium. Repair broken latch on the entry door of the boy`s locker room. Repair broken door latches on the entrance door from the main hall to the 200 wing and on the rear exit door to the deck of modular #4. Replace missing floor tiles beneath drinking fountain in the hallway of modular #1. Replace broken floor tile at the rear entry doorway of modular #1. Replace bent and damaged exterior exit door thresholds in the cafeteria dining room. 15.0
7. Textbooks were stored in the staff bathroom of modular class building #1. Bathrooms are not clean storage spaces for classroom supplies. 10.0
8. Repair loose support cable for suspended ceiling light fixture in the corner of the media center. Priority repairs for safety are required to prevent the possibility of this ceiling light fixture from collapsing from above. Multiple ceiling lights are nonfunctional in the media center, the cafeteria dining room, and in the auditorium and stage area. Visibility is poor in the auditorium due to the poor lighting. Priority repairs are needed. Six ceiling lamps in the auxiliary gym are nonfunctional and require replacement. Dust build up is present on top of the ceiling ventilation ductwork in the cafeteria. These vent ducts surfaces require cleaning. Repair nonfunctional ceiling lights in the modular #2 girl`s bathroom and in the modular #4 boy`s bathroom. Visibility is low in these bathrooms due to poor lighting. 20.0
General Comments
School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 02/08/2021
Score: 93

#  Comments Points
4. Repair nonfunctional toilet in the second stall of the boys bathroom #2207. Repair leaking toilets in the first stall of the girls bathroom #2211, in the office staff bathroom #100N, and in the second stall of the modular building #4 girls bathroom. Repair toilet in the second stall of the girls bathroom #2311. This toilet has poor water flow. 20.0
5. Repair hand wash sink faucet in girls locker room #424A bathroom area. This hand sink faucet has poor water flow. Repair leaking sink faucets in the following science lab classrooms: lab classroom #204, (one leaking faucet), lab classroom #322, (three leaking faucets), lab classroom #2326, (three leaking faucets). Repair clogged sink drain in art classroom #304. Repair clogged sink drains in science lab classroom #3204. (Priority repair. All the sink drains in this science lab classroom are clogged and require immediate repair.) Repair nonfunctional sink faucet that has poor water flow in girls bathroom #2211. Repair damaged interior of cabinet beneath sink located in home economics classroom #2222. Repair broken faucet control valves on hand wash sinks in the girls bathroom in modular building # 3 and in the boys bathroom in modular building #2. Both sink valves are designed to automatically shut water flow off but do not stop running when pressed. 15.0
6. Repair ceiling leaks in the hallways at girls bathrooms #503 and girls bathroom #604. Repair ceiling leaks in the gym area women`s faculty bathroom #403 and in the boys locker room #416 shower area. The ceiling paint is chipping at this leak location in the boys locker room and requires repair. Repair broken shower wall tile on the first shower stall in boys locker room #418. Seal cracks in the shower wall tile in two shower stalls also located in boys locker room #418. Repaint shower area wall in girls locker room #420. This wall area was recently repaired but was not painted to make it water proof. Repair chipping ceiling paint in the (gym/room #105) over the bleachers . Repair ceiling/roof leaks in the media center, in stairway #4 on the top floor landing at the 3300 hall entry, in stairway #1 on the top floor landing at the entry to the 3200 hall, and in stairway #3 above the top floor landing. Repair chipped ceiling paint in all of these stairways after the leaks are repaired. Repair damaged and broken floor tile in the special needs kitchen class bathroom #222B. Repair ceiling leak in the special needs class kitchen #222. Repair ceiling leak in the art class kiln room #304A. Repair ceiling leaks in science lab classrooms #3200 and #3202. Repair ceiling leaks in the 3300 hall at the entrance to stairway #4, at mechanical room #M-15, and at classroom #3306. Repair ceiling leak in staff bathroom #2313. Water stained and damaged ceiling tiles should be replaced after the sources of all ceiling leaks have been repaired. 15.0
8. Replace broken ceiling light shields in cafeteria dining room. Replace missing ceiling light shield in auditorium stage dressing room #500A. Repair nonfunctional ceiling light in boys bathroom #307. Replace missing ceiling fan/vent covering in the modular building boys bathroom #M-803-02A. 20.0
General Comments
Sewer gas odors were present in the gym faculty locker room #402 shower, in the boys locker room #416 showers, and in the boys locker room #418 bathroom stalls. The sewer gas odors are coming from the floor drains in these locations. Custodial staff should pour water down these drains regularly to keep the drain pipes from drying out and allowing a passage of sewer gas into the building. The changing table in the special needs class bathroom #222A has a torn covering and requires replacement. School facility sanitation inspection completed.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 05/24/2017
Score: 88

#  Comments Points
3. Adjust water pressure on fountains to avoid mouth contact on spout (Modular 1, Modular 2, Modular 4, 1st floor, 2nd floor and 3rd floors). Also several water fountains in need of cleaning around the mouth area. A few water fountains not working in Modular 4 and the 3rd floor intersection where 200 and 300 wings meet. 40.0
4. Toilets are broken in the following areas (one stall ladies restroom 2311, Modular 1- two toilets in the ladies restroom are not working, Modular 3-three toilets in the ladies restroom non operational and Modular 3-one toilet in the men's restroom). All toilet fixtures must be kept in good repair, please repair. 20.0
6. Water leak and mold beginning to form on ceiling next to room #322 and ceiling tile water damage next to room S8. Small stains in carpet in the following areas; (media room, room #3212, #3220,and #312). 15.0
7. Elevate storage 15" off floor in storage rooms to facilitate cleaning in classrooms, trailers, and storage closets. 0.0
8. Ceiling air intake grids need cleaning in many rooms (trailer 7, restroom 109, shower room 420 and #3209. Dead bugs in light fixture (shower room 420, on wall next to cisco device Trailer 3 and dead bugs in light fixture Trailer 3. A few lights burnt out in the following areas..(trailer 13-1, trailer 4-2, trailer 5-1, 1st floor hallway 300 wing. Please keep ventilation and light fixtures clean and in good repair. 0.0
9. There is damage to the top of the divided tall wall in Shower room #420 Area open around escutcheon on wall in shower room #420. Light lens cracked in dressing room 418.Water pressure lacking at sinks (one shower stall #420 and one sink in room #424). One shower head is missing (shower stall #420) Calcium buildup on shower handle in shower room men's 418 and Room #424. Please ensure light fixtures are clean and kept in good repair. 15.0
11. Improper chemical storage observed on top of counters and unlocked classroom cabinets. Chemicals must be stored according to manufacturer’s instructions. Chemicals labeled " keep out of reach of children" with no other warnings is to be kept 5 feet or higher off of the floor when not in use. These chemicals include hand sanitizer, disinfecting wipes, and some lotions. Chemicals with other warnings in addition to " keep out of reach of children" or “keep inaccessible to children” are to be kept locked. These would include betadine solution, cleaning compounds and anything in an aerosolized. 30.0
General Comments
Trailer 15 is having heating and cooling issues according to a Teacher.
A few mats are frayed on the edges in the gym storage room.
Wood walkup and wood hand rails to a few of the exterior structures are in disrepair at Trailer 3, Restroom Trailer, Trailer 7 and Modular 1. Wire fencing at the staircase near the dumpster rear of the building is in disrepair. Please repair.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 10/25/2013
Score: 91

#  Comments Points
3. Adjust water pressure on fountains to avoid mouth contact on spout. (1st floor, 2nf floor burg wall). Several fountains not working. Clean where pink mold visible around spout (M803). 20.0
5. Art Room-sink nearest door has major leak underneath-repair as soon as possible. Modular #1 right girl's handsink very slow to drain. Hall 300 (1st floor) Left Boy's handsink pressure too high-spraying out of sink. Faucet (handsink) constantly leaking in bathroom b/w room 220 and 224. 15.0
6. Floor tiles around leaking sink in Art Room coming up-possibly due to handsink leak. Water leak and mold present on ceiling in R322 outside wall and in women's team locker room 424. 15.0
7. Elevate storage 15" off floor in storage rooms to facilitate cleaning. 10.0
8. Ceiling air intake grids need cleaning in many rooms (media center, 2104, 2320, 3208, 3218, 3214, etc.) 20.0
11. Observed roach harborage and breeding in Custodial 209. Behind buffer pad stored on top of faucet. Eliminate roaches. 10.0
General Comments
5. Repair/replace both towel dispensers in Art Room.
Repair announcement speaker in trailer 15.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 10/29/2010
Score: 91.5

#  Comments Points
4. Visible mold and build up present on urinals (@ water discharge and under neck)and in toilets (all around rim where water discharges). 20.0
6. Repair transition strips (1 in auditorium, 2 leading into classrooms first hall). Fix ceiling leaks in following areas: 2100 hall, R3308, R3310, Big and Small gyms, gym hall, repair walls in modular trailer (room 6) and floor transition strip. repair water damaged door frame of men`s bathroom in trailer. 15.0
7. Elevate storage off floor (at least 15 inches in equip rooms and storage rooms) 10.0
8. Clean all vents in modular and trailers. Clean vents in media room. 20.0
9. Replace missing shower wand, replace missing shower curtains, repair showers and sinks not working. 20.0
General Comments
Clean water fountains in modular units. **Teacher requested air quality inspection in modular (Foreign language building).
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 01/30/2007
Score: 90.5

#  Comments Points
4. Repair nonfunctional commode in girls bathroom on second floor hall. 20.0
5. Repair or replace damaged towel dispensers in restrooms for students throughout facility. Automatic hand blowers may be an option if students continue to vandalize towel dispensers. 20.0
6. Repair facility ceiling leaks and replace water damaged ceiling tile. Ex: Rooms # S14, 2104, 2308, 3208, and second floor computer room. Leaks are also present on third floor hallway at mechanical room # M15 and in hallway to music rooms. 15.0
8. Clean ceiling vents in second and third floor classrooms. Ex: Home economics, class and computer rooms, Verify that vent filters are changed regularly and duct work is cleaned. Some second and third floor vent returns have blown dust onto surrounding ceiling areas. 20.0
9. Repair nonfunctional handwash faucet in boys locker room. 20.0
General Comments
Repair nonfunctional water fountain in hall by cafeteria dining hall and atheletic wing. Cleaning chemicals must be stored out of reach of students in classrooms. Ex: Store cleaning products in cabinets, closets, or storerooms. If science faculity are keeping class pets like reptiles students must wash their hands immediately after touching these animals due to the risk of salmonella infection. Thermometers are needed in home economics class refrigerators to verify that cold foods like eggs are being kept at a temp. of 45 degrees F. or less. Repair leak on water heater in mechanical room # M12. Contact Wake County Environmental Services to obtain a permit to legally prepare and sell food like hotdogs at the stadium concession stand for sports seasons.
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 06/04/2004
Score: 98

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment

Green Hope High School
Location: 2500 Carpenter Upchurch RD CARY, NC 27519
Facility Type: Schools
Inspection Date: 11/01/2001
Score: 95

#  Comments Points
General Comments
Red Denotes Critical Violation
View Last 3 Inspections for this Establishment


Keyword (1):
Keyword (2):
Keyword (3):
Score Range:
-
Establishment Type:
Zipcode:
Violations:
Date Range:
- - Start
- - End

Health Inspections Home :: FAQ